Business Type:
Manufacturer/Factory,Trading Company
Business Range:
Vacuum Circuit Breaker, Ring Main Unit, Earthing Switch, Switchgear Cabinet
Establishment:
2010
R&D Capacity:
OwnBrand, ODM, OEM
Terms of Payment:
LC, T/T
Main Markets:
South America, Europe, Africa
OEM/ODM Service
Sample Available

Vcb, Circuit Breaker, Indoor Medium manufacturer / supplier in China, offering 12kv Indoor Medium Voltage Vs1 Type Vacuum Circuit Breaker, Medium Voltage 12kv Withdrawable Embedded Pole Type Vacuum Circuit Breaker, Gcs II Low Voltage Switchgear Cubicle and so on.

1
    YRS
General Supplier
Supplier Homepage Electrical & Electronics Breaker & Protector Circuit Breaker 24kv Indoor Mv Assembly Type Vacuum Circuit Breaker   Vs1 Series

24kv Indoor Mv Assembly Type Vacuum Circuit Breaker   Vs1 Series

Get Latest Price
Min. Order / Reference FOB Price
1 Piece US $1200.00/ Piece
Local Area: Wenzhou, Zhejiang, China
R&D Capacity: OEM, ODM, Other
Payment Terms: LC, T/T
Breaking Capacity: Middle Voltage
Operation: Energy-storage Type
Speed: High-Speed Circuit Breaker
24kV Indoor MV Assembly Type Vacuum Circuit Breaker VS1 Series ASTA certifiedProduct overviewVS1 series embedded pole vacuum circuit breakers are applicable to 24kV, three-phase AC 50Hz indoor switchgear components and can serve as protection and control units for industrial and mining establishments and power transformer substation equipments. With modular and independent-frame design for their spring operating
mechanisms, VMG circuit breakers can operate with KYN28-24 mid-set and fixed switchgear cabinets. These circuit breakers are subject to both fixed installation and assembly with chassis as a handcart unit.Normal service condition
Altitude: ≤1000mAmbient temperature:
Maximum temperature +40ºC
Minimum temperature -15ºC
Average air temperature(24-h) +35ºCAmbient humidity:
Maximum average humidity
24 hours ≤ 95%
1 month ≤ 90%Maximum water vapor pressure
24 hours ≤ 2.2kpa
1 month ≤ 1.5kpa
Solar radiation is negligible.
Vibration from the outside of switchgears and control-gears is negligible. The ambient air has no obvious pollution of dust ,smoke, corrosive or combustible gases, steams or smog.Human-oriented design
VS1 series vacuum circuit breakers are Murge's independently developed new generation of medium-voltage embedded pole models, which have applied for many technical patents, past a package of type tests of the National High-voltage Quality Monitory and Inspection Center and obtained ASTA international certification. The
products feature beautiful shape design, easy operation, high reliability and long service life.Class M2, C2 and E2 model
VS1 series vacuum circuit breakers are available in specific environments, free of maintenance and capable of frequent operation. Compared with traditional circuit breakers, these breakers have their mechanical endurance raised to 20,000 ops from 10,000 ops with an enormous improvement. The type test for capacitive current breaking shows an extraordinarily low re-striking probability. These products feature prolonged electrical endurance and free maintenance.VS1 circuit breaker features high stability and high reliability
In terms of mechanisms, VS1 series vacuum circuit breakers are given special optimization totransmission parts. Modular spring mechanisms have such advantages as convenient maintenance, short power-off maintenance, high versatility of parts, and boast better compatibility with vacuum interrupters, which greatly improves the technical parameters and delivers more excellent performance.Applicable standards
IEC62271-100 High-voltage switchgear and control-gear-Part 100: Alternating-current circuit- breakers.Secondary circuit
VS1 series vacuum circuit breakers adopt modular design for their secondary control circuit boards. The electric connection of the mechanisms employs high-grade self-fastened plugs, which both facilitates replacement and ensures reliable electrical connection.High-performance oil buffer
High-performance breaking buffer can markedly reduce the overshoot and rebounding amplitudes of the moving contact of a vacuum circuit breaker in breaking, thus avoiding the loss of mechanical endurance due to partial over fatigue of vacuum interrupter bellows resulting from moving contact overshoot. As the rebounding amplitudes of the moving contact reduces, no re-ignition and restrike is found during the switching capacitor bank test.Technical Parameters
Sr. NODescriptionUnitData
1Rated voltagekV24
2Rated frequencyHz50/60
3Rated currentA6306301600
4125012502000
5Power frequency withstand voltage 1min.kV65/79
6Lightning impulse withstand voltagekV125/145
8Rated short circuit durations4
10Rated short-circuit breaking currentkA202531.5
11Rated short time withstand currentkA202531.5
12Rated short-circuit making currentkA506380
13Rated peak withstand currentkA506380
14Rated short circuit durations4
15Rated operating sequenceO-0.3s-CO-180s-COO
16Rated short circuit breaking timestimes20
17Mechanical enduranceOps10000
18Rated single capacitor bank breaking currentA630
19Rated back-to-back capacitor bank breaking currentA400
20Allowable wearing thickness between moving and fixed and contactmm3