Transformerless High Frequency online UPS 10K- 80KVA with IGBT TechQuick View
1: China UPS with good quality and low price, same quality like APC, Eaton, MGE UPS.
2: 3 Phase UPS with 50Hz / 60Hz Frequency and 380V / 400V / 415VAC Input and output
3: Triphase UPS withEmergency power off function (EPO)
3: UPS with SNMP , USB , RS232 Ports
4: UPS with Parallel Redundancy Function
UPS Key Features True double-conversion.DSP technology guarantees high performance.Output power factor 0.8.Active power factor correction in all phases.50Hz/60Hz frequency converter mode.Accepts dual-mains inputs.Generator compatible.SNMP+USB+RS-232 multiple communications.3-stage extendable charging design for optimized battery performance.Adjustable battery numbers.Maintenance bypass available.Optional N+X parallel redundancy.
Technical SpecificationModel33Q10KL33Q 20KL33Q 30KL33Q 40KL33Q 60KL33Q 80KLCommentsInputInput voltageRated voltage380VAC/220VAC380VACPhasethree phase with groundTurn on voltage range(120±5~274±5)VAC(207±9~475±9)VACBypass voltage range(60±5~300±5)VAC(105±9~518±9)VACCould be adjusted by software.Bypass
low loss60VAC~220VAC(default 60VAC)105VAC~380VAC
(default 105VAC)Bypass low comebackLow loss +5VACLow loss +17VACBypass high loss220VAC~300VAC(default 300VAC)380VAC~475VAC
(default 475VAC)Bypass high comebackHigh loss -5VACHigh loss -17VACLine low loss
/comeback(120±5) VAC /(140±5) VAC(207±9) VAC /(242±9)VACload≤50%(140±5) VAC /(160±5) VAC(242±9) VAC /(276±9)VAC50%<load ≤90%(160±5) VAC /(175±5) VAC(276±9) VAC /(302±9)VACload>90%Line high loss/comeback(275±5)VAC/(260±5)VAC(475±9)VAC/(449±9)VACInput frequencyRated frequency50HzFrequency
low loss(40~49) ±0.2Hz(default:46Hz)Could be adjusted by software.Frequency
low comebackFrequency low loss +0.5HzFrequency
high loss(51~60)±0.2Hz(default:54Hz)Frequency high comebackFrequency high loss -0.5HzInput power factorInput power factor> 0.9933Q 10-40KL:220VAC,full R load
33Q 60-80KL: 380VAC,full R loadGeneratorSupport generator inputGenerator rating≥2*UPS ratingInput currentRated current14A28A42A67A80A105AInput THDI<= 10%Output protectionRating protection32A
Breaker50A
Breaker60A
Breaker80A
Breaker100A
Breaker125A
BreakerOutput powerVA/watt10KVA/8KW20KVA/16KW30KVA/24KW40KVA/32KW60KVA/
48KW80KVA/
64KWRated voltage220VAC380VACSine waveVoltage range200/208/220/230/240VAC345/359/380/397/415 VAC33Q 10-40KL: Could be adjusted by software. 10% derating for 208VAC/200VAC.
33Q 60-80KL: Could be adjusted by software. 10% derating for 345VAC/359VAC.Voltage regulation±1%Voltage distortion≤5%≤10%Full RCD load≤3%Full R loadDC offset≤200mVTransient response≤9%R load0%~100%~0%≤6%R load 20%~100%~20%Transient recovery≤60ms voltage recovery to 90%Full RCD loadBypass output
before turn-onYESCrest ration3:1Output frequency rangeNormal mode1,Same as input frequency(46Hz~54Hz)
2,50Hz(Input frequency>54Hz or Input frequency<46Hz)Battery mode(50±0.1) HzSlew rate1 Hz/SecEfficiencyNormal mode> 93%> 90%Battery mode> 90%> 90%OverloadNormal mode
/battery modeOverload warning only105%±5%≤load1min,then transfer to bypass and alarm.105%±5%30S,then transfer to bypass and alarm.125%±5%300mS, then transfer to bypass and alarm.load>150%±5%Automatically retransferYESShort protectionNormal/
battery modeYESTransfer timeNormal to battery mode0mSBattery to normal mode0mSNormal to bypass mode<4mS0mSBypass to normal mode<4mS0mSBattery and chargerBatteryRated voltage192VDC240VDC192VDC*2192VDC*2480VDCType/RatingBattery quantity162016*216*240Backup timeProtectionLow alarm voltage /comebackvoltage(180.8V±4V)/ (188.8V±4V)(226V±4V)/ (236V±4V)(180.8V±4V)/ (188.8V±4V)(226V±4V)/ (236V±4V)(452V±4V)/ (472V±4V)33Q 30KL use twoShutdown voltage/ comeback voltage160V±4V/168V±4V(200V±4V)/ (210V±4V)160V±4V/
168V±4V(200V±4V)/ (210V±4V)(400V±4V)/ (420V±4V)DC protectionOvercharge protection/ comeback voltage(249.6V±4V)/
(216V±4V)(312V±4V) (270V±4V)(249.6V±4V)/ (216V±4V)(312V±4V) (270V±4V)(624V±4V) (540V±4V)Leakage current< 500uAOver discharge protection14.5hCould be set by softwareBattery testBattery weakYESBattery faultYESChargerOutput voltage(219.2±3)VDC(277±3)VDC(219.2±3)VDC(277±3)VDC(554±3)VDCCharge timeDepends on the external battery capacityCharge current7.5A6A5A4A10AInterfaceAlarm silenceYESDC power
turn-onYESAutomatically retransferYESAudio alarmBattery modeBeep/4sBattery low/
charger faultBeep/1sUPS faultContinue beepOverloadBeep/1sBypass modeBeep/2MinL/N inverseBeep/2MinCommunicationRS232 interfaceYESIntelligent slotYESMonitor softwareAppending with UPSCoolingForce air coolingDisplayLCD/LED displays UPS statusEnvironmentWork temperature0ºC~40ºCAltitude<1000mAudible noise≤60dBStorage temperature-15ºC~45ºCWork humidity20%~95%StandardEMSESDIEC61000-4-2Level4RSIEC61000-4-3Level3EFTIEC61000-4-4Level4SurgeIEC61000-4-5Level4EMIConductedEN55022Class ARadiatedEN55022Class ASafetySafetyGB4943-2001/IEC62040-1Machinery featuresSizeOutline dimension and net weightL*W*H (mm)710*260*717840*515*1135Net weight(Kg)45/9350/98195208Optional functions60HzOptionalSet by softwareConverter modeOptionalSet by softwareECOOptionalOptionalAvailable and set by softwareEPOOptionalOptional*Specification is subject to change without further notice