Supplier Homepage Electrical & Electronics Breaker & Protector Circuit Breaker 3p 4p DC MCCB Moulded Case Circuit Breaker 1500V

3p 4p DC MCCB Moulded Case Circuit Breaker 1500V

Get Latest Price
Min. Order / Reference FOB Price
1 Piece US $30.00/ Piece
Local Area: Wenzhou, Zhejiang, China
R&D Capacity: OEM, ODM, Other
Payment Terms: LC, T/T, D/P, PayPal, WesternUnion, Small-amountpayment
Structure: MCCB
Type: Circuit Breaker
Function: Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvo

DC system-specific circuit breakers are used in rated insulation voltage of 1600V and a rated operating voltage of DC1500V and below, and rated operating currents of 250A and below. C ircuit breakers are mainly used for overload and short circuit protection of distributed power and protection circuits and power equipment in DC systems . U nder normal circumstances can be used as a line of infrequent conversion and DC motor infrequent start.

1.Normal conditions of use

Ambient air temperature does not exceed the upper limit of +70ºC, the lower limit of not less than -40ºC , 24-hour average does not exceed +35ºC. (Note: Circuit breakers for use in ambient air temperatures above + 70ºC or below -40ºC should be consulted with the manufacturer);
The installation site of the altitude does not exceed 2000m (2000m above the need for the corresponding derating)
The relative temperature of the atmosphere is not more than 50% at the highest temperature around +40ºC, and can be compared at a lower temperature.High relative humidity (for example, 90% at 20ºC), and the consideration of temperature change on the surface of the product dew.
2.Normal installation conditions
Installation conditions: the general should be vertical installation or horizontal installation;
Installation categories: Class III of circuit breaker main circuit, control circuit and auxiliary circuit are class II.
Pollution level: Three
3.Normal storage and transport conditions
The temperature limit is not lower than -40ºC,the upper limit does not exceed +70ºC Relative humidity (25ºC) does not exceed 95ºC;
The product should be lightly moved during transport,should not be reversed should be acoided violent collision Main technical parameters

Main technical parameters

framelevel250ARatedworkingvoltageDC500V/DC1000VDC1250V/DC1500V
Ratedworkingcurrent(A)100/125/140/160
/180/200/225/250
RatedinsulationvoltageDC160
Polenumber2Arcingdistance≤50mm
BreakingcapacityIcu=Ics=15kAMechanicallife200
Shortcircuit
instantaneoussetting
5~10DegreeofprotectionIp20
StandardruleGB14048.2IEC60947

Description of protection

Overload long delay protection

AmbienttemperatureTestcurrentAppointmenttimeStartingstate
+50ºC±2ºC1.05In≥NoactionColdstate
1.3In<2hactionHotstate

Short-circuit transient protection

AmbienttemperatureTestcurrentAppointmenttimeStartingstate

+10ºC~+40ºC

4Inor8In≥200msNoaction
6Inor12In<200msaction

Derated coefficient when ambient temperature changes

Ambienttemperature40ºC45ºC50ºC55ºC60ºC65ºC
Deratedcoefficient1In0.97In0.93In0.89In0.85In0.82In

A comparative relationship between the rated current of a circuit breaker and the cross section ofa linked wire

Ratedcurrent100A125A140A160A180A200A225A250A
Cableinterceptingarea35mm²50mm²70mm²95mm²120mm²

.High altitude derated coefficient

Altitude2000m3000m4000m5000m
Operatingvoltagederatingcoefficient10.90.80.7
Operatingcurrentderatingcoefficient10.960.930.9