Sectionalizer, Auto Circuit Breaker, Distribution manufacturer / supplier in China, offering 15kv/27kv/38kv Recloser Wtith IEC61850 and DNP3.0 for Distribution and Substation, Pasgt Tactical M88 U. S. Army Steel Replica Anti-Riot Helmet Full Head Coverage with Adjustable Chin Strap for Personal Safety of Airsoft Hunting Paint Ball Bb, Od8mm Stainless Steel Bowfishing Line Guiding Rod with Ceramic Eyelet Accessory Fit Reel Seat Mount for Fishing Bow Fishing Slingshot and so on.

1
    YRS
General Supplier
Supplier Homepage Electrical & Electronics Breaker & Protector Circuit Breaker 66kv to 500kv Different and Busbar Protection of Power Transformer

66kv to 500kv Different and Busbar Protection of Power Transformer

Get Latest Price
Min. Order / Reference FOB Price
1 Piece US $10.00/ Piece
Local Area: Ningbo, Zhejiang, China
R&D Capacity: OEM, ODM, Other
Payment Terms: LC, T/T, PayPal
Task: Program
Structure: Combination
Mathematical Model: Linear

RELAYS IED´S FEEDER
69KV FEEDER PROTECITON REALY
QUANTITY
4
YES
MOUNTING
INCLUDING WHERe CENL EP ESMERALDAS INDICATE
YES
LOW FREQUENCY
81
YES
OVERCURRENT; CURVES ANSI - IEC
50/51
YES
50N/51N
YES
5OG / 51G
YES
Breaker fault
50 BF
YES
AUTORECLOSER
79, MINIMUM 4 OPERATIONS
YES
COULD LOAD PICK UP
YES
DIRECTIONAL; FORWARD AND REVERSE
67
YES
ADJUSTMENT GROUPS
3
YES
LOW VOLTAGE
27
YES
SURGE
59
YES
HARMONIC
Restriction of harmonics
YES
HIGH IMPEDANCE FAULT
PROTECTION FAULT FROM LOW IMPEDANCE IN THE DISTRIBUTION LINES.
YES
CURRENT
I
YES
VOLTAGE
V
YES
POWER FACTOR
FP
YES
POWERS
ACTIVE, REACTIVE AND APPARENT
YES
OPEN
YES
CLOSE
YES
TRIGGER
TRIPOLAR
YES
OSCILOGRAFIAS
Pre fails - post failure
YES
DATE
YES
TIME
YES
FAULT CURRENT SEQUENCE +, - AND 0
YES
FAULT SIGNALLING
USE OF LED
YES
DIGITAL INPUTS
16 MIN
16
DIGITAL OUTPUTS
6 MINIMUM
10
CURRENT NOMINAL SECONDARY
1-5 AMP
YES
ADJUST TAP
LESSER or equal 0.5 In
YES
STANDARDS
ANSI-IEC
YES
POWER SUPPLY 1
80-240 VDC
YES
POWER 2
80-240 Vac
NON
SUPPLY TECHNOLOGY
DIGITAL MICROPROCESSOR
SELF-TEST
YES
PULSES OF VOLTAGE
DIGITAL INPUT, DIGITAL OUTPUT
YES
BLUETOOTH
APPLY FOR PLACED RECLOSERS
ALONG THE FEEDER, REACH 20 M
YES
10 years
MINIMUM
YES
TERMINAL TEST - SHORTCIRCUITABLE
YES
TERMINAL TEST - SHORTCIRCUITABLE
SHORTCIRCUITABLE TERMINALS AND TESTS SHOULD COME WITH THE INSTALLATION MANUAL IN SPANISH, THE TERMINAL BOARD MUST BE ABLE TO WITHSTAND VALUE OF INJECTION OF SEConDARY CURRENT MINIMUM 100 A. IS ACCEPTED THAT THE TWO TERMINALS COME IN A SINGLE ELEMENT, IN CASE THAT THE PURCHASE INCLUDE BOARD POSITION, TERMINALS MUST BE ALREADY INSTALLED AND READY TO OPERATE. THE PROTECTIONS OF CNEL EP GROUP WILL CARRY OUT INJECTION TESTING ALTOGETHER WITH A TECHNICIAN OF MANUFACTURES OR SERVICEMAN OF THE OFFEROR AND VERIFY THE OPERATION THEREOF IN ConJUNCTION WITH THE PROTECTION RELAY.
YES
CERTIFICATE OF SOLE AUTHORIZED REPRESENTATIVE OF THE
BRAND PROTECTION RELAYS
OK
YES
CERTIFICATE KEMA IEC 61850-6, 7-1, 7-2, 7-3, 7-4 and 8-1
OK
YES
CERTIFICATES STANDARD ISO 9001
OK
YES
YES
TRAINING CERTIFIED IN SPANISH LANGUAGE WITH CERTIFIED INSTRUCTOR FROM FACTORY
1 training 5 days, after that the OFFEROR is required to give training for a year until they are solvent doubts IED´s. this under prior coordination with the administrator of the contract of CNEL EP, these skills will be two-day minimum 5 times A year, to failure to comply with this shall present his bad CUMPLIEMIENTO for future contracts offered by CNEL EP.
YES
2 SUBJECT PROTECTIONS SETTINGS, THE PERSON WHO WILL GIVE THE TRAINING MUST BE PROTECTIONS ENG. AND SHOULD BE IN FULL KNOWLEDGE OF THE SUBJECT, ABLE TO RESOLVE ALL QUESTIONS SUBMITTED AT THAT TIME.
YES
3. COMMUNICATION TO THE ConTRACT ADMINISTRATOR
YES
4. IEC 61850, WANT TO MAKE AN EXAMPLE
TWO IED´s this should be demonstrated and
IN FULL ACCEPTANCE OF THE GROUP
ASSISTANT TO THE TRAINING.
YES
5. EVIDENCE OF CURRENT INJECTION
YES
6. INSTALLATION ON THE SAME FIELD, IF IT
REQUESTED SEVERAL INSTALL ONE AS EXAMPLE, PART OF THE TRAINING.
YES
LICENSE
FREE (N NUMBER OF USERS)
YES
LOCAL TECHNICAL SUPPORT
ADDRESSES, PHONES, RESPONSIBLE
WITH STAFF TO SUPPORT TECHNICIAN, document NOTARIZED SIGNATURE
YES
MANUAL
Spanish
English
AMBIENT TEMPERATURE
MORE THAN 40 DEGREES, LESS THAN 10
YES
PORTS
TYPE
DEscriptION
FRONT
RJ-45, RS 485
FIELD CONFIGURATION
RS232
2 PORTS, REAR
ETHERNET
NETWORK ConFIGURATION WITH REDUNDANCY DOUBLE OR RING, SCADA INTEGRATION CONFIGURATION
YES
2 PORTS, REAR
FIBER OPTICS
NETWORK ConFIGURATION WITH REDUNDANCY DOUBLE OR RING, SCADA INTEGRATION CONFIGURATION
YES
1 PORT
DB9-IRIG-B
TIME SYNCHRONIZATION
YES
3 PORT
RS-485
THE SCADA INTEGRATION
YES
CALIBRATION AND TESTING
OK
THE ConTRACTOR MUST GIVE IT
YES
SETTINGS
OK
CNEL EP ESM
YES
YES
MODBUS/TCP, DNP3/LAN/WAN, FTP, TELNET, PING, IEC 61850
YES
YES
DNP3, MODBUS RTU,
YES