Fire Alarm System, Control System, Fire Alarm manufacturer / supplier in China, offering Wired Addressable Control Panel Fire Alarm System, 2-Wire Conventional Fire Alarm Control Panel for Hotel Use, Asenware Manufacturer Addressable Fire Alarm Control Panel for Office Building and so on.

1
    YRS
General Supplier
Supplier Homepage Instruments & Meters Detector Fire Alarm & Smoke Detector China 1-32 Zone Conventional Fire Alarm Control Panel

China 1-32 Zone Conventional Fire Alarm Control Panel

Get Latest Price
Min. Order / Reference FOB Price
1 Piece US $525.00/ Piece
Local Area: Shenzhen, Guangdong, China
R&D Capacity: OEM, ODM, Other
Payment Terms: LC, T/T, PayPal, WesternUnion
Type: Fire Alarm
Anti-theft Alarm System Approach: Active
Anti-Theft Alarm System Type: Sound and Light Alarm
1-32 Zone Conventional Fire Alarm Control Panel
Introduction:
1 AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4 standard.
2 It is modularized design, the panel can expend from 1 zone to 32 zones easily.
3 It has 2 level control mode by a lock
4 It has 24VDC and 5VDC power supply output.
5 It has FIRE and FAULT signal output.
6 It has 2 general sounders output.
7 Each zone has 1 circuit detectors input.
8 Each zone can be disable by a button.
9 It has RESET button to reset the panel.
10 It has SILENCE button to stop BUZZER and SOUNDERS.
11 It has EVACUATE button to start a manual fire alarm immediately.
12 It has battery low protection function, when battery voltage lower than 21VDC, battery will be cut off automatically until the mains power is on.
13 It has an optional GSM module for fire alarm by SMS.
14 It is economic, user-friendly and easy maintenance.
Parameters:

ITEM1Zone panel2Zone panel4-8 Zone panel12-32 Zone panelModel No.AW-CFP2166-01AW-CFP2166-02AW-CFP2166-04-8AW-CFP2166-12-32Power specification
Mains supply voltage110VAC or 240VACInternal power supply27.2VDCTotal output current limited500mA @ 240VAC500mA @ 240VAC3A @ 240VAC3A @ 240VACMain supply monitor for faultYesBattery protection for low voltageYesBatteries (default configuration)12V2AH*2Detector circuit specification
Number of circuit124-164-32Line fault monitor for open circuitYesLine fault monitor for short circuitYesLine fault monitor for detector removalYes, if End of Line Monitor Unit fitted in place of End of Line ResistorEnd of Line device6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)Detector continuity diodesSilicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted to give Detector Removal Fault)Call point resistor value470 to 680 Ω, 0.225 or 0.5 wattMaximum number of smoke/heat detectors per zone20 (based on a total detector current of 2mA, each detector consuming 100μA).Note: if End of Line Monitor Unit is fitted, for correct operation maxmum voltage drop must not exceed 12 volts.Maximum number of manual call points per zoneNo limitSounder circuit specification
Number of general circuits2End of line resistor value6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)Line fault monitor for open circuitYesLine fault monitor for short circuitYesOutputs fused AT400mAMaximum number of bells @ 20mA of each sounder output20Fuses
Battery fuse1.5A F 20mmSounder outputs500mA F 20mmFire and fault output
Output typeNC and NO relayMaximum current100mAConnection block
Largest acceptable conductor size2.5mm2Smallest acceptable conductor size0.75mm2Size and weight

Dimensions(mm)272*200*70mm320*231*90mm395X502X124362X565X124Weight (without batteries)4kg5kg7kg8kgWeight (with batteries)5.8kg6.8kg9.6kg12.5kg