MAIN TECHNICA DATA
Rated voltage12KV(1min)
Short-time(1min) power-frequency withstand voltage42KV
Rated current1600/1250A()
Lighting impulse withstand voltage(peak)75KV
Rated frequency50HZ
Circuit resistance at rated contact force≤15μΩ
Rated short-circuit breaking current25KA
Mechanical life20,000
Operations of short-circuit breaking current interruption50
Contact closing force due to bellows and atmosphere100±30N
Rated short-circuit making current63KA
Counterforce at rated contact stroke200±30N
Rated peak withstand current63KA
Contact limit erosion3mm(4)
Rated short-time withstand current(4s)25KA
Shelf life20
Rated single capacitor bank breaking current630A/
Weight/mass of moving parts3Kg/1.1Kg
Rated back-to-back capacitor breaking current400A
Rated operating sequenceO-0.3s-CO-180s-COMECHANICAL DATA OF CIRCUIT-BREAKING EQUIPPED WITH THE INTERRUPTERS
Rated contact stroke9±1mm
Rated operation pressure of contact2400±200N
Contact connection stroke4±1mm
Bounce duration of contact closing≤2ms
Average opening speed1.1±0.2m/s
Out of simultaneity of contact closing and opening≤1ms
Average closing speed0.6±0.2m/s
Max. overtravel≤2mm