Sectionalizer, Auto Circuit Breaker, Distribution manufacturer / supplier in China, offering 15kv/27kv/38kv Recloser Wtith IEC61850 and DNP3.0 for Distribution and Substation, Pasgt Tactical M88 U. S. Army Steel Replica Anti-Riot Helmet Full Head Coverage with Adjustable Chin Strap for Personal Safety of Airsoft Hunting Paint Ball Bb, Od8mm Stainless Steel Bowfishing Line Guiding Rod with Ceramic Eyelet Accessory Fit Reel Seat Mount for Fishing Bow Fishing Slingshot and so on.

1
    YRS
General Supplier

China 12kv Power Mounted Transformer

Get Latest Price
Min. Order / Reference FOB Price
1 Piece US $5000.00/ Piece
Local Area: Ningbo, Zhejiang, China
R&D Capacity: OEM, ODM, Other
Payment Terms: LC, T/T, PayPal
Application: Power, Lighting
Phase: Three
Core: Core-type Transformer

.

ClauseDescriptionSPECIFICAITON

1.Scope

1.1.Supply of i. hermetically sealed oil-immersed distribution transformers

1.2. ii.for continuous service on 11kV, 3 phase, 50Hz system

1.3.iii.suitable for the following climatic conditions:

1.4.

a.Ambient shade temperature: 5 °C – 45°C

1.5.b.Relative humidity: 50% – 95%

1.6.c.Atmosphere: Heavily polluted and saline

1.7.iv.suitable for Installation: Outdoor – Pole mounted

1.8. General Transformer Requirements

1.8.1.Standard Latest editions of IEC 60076

1.8.2.Type of transformerThree phase with separate primary and secondary windings

1.8.3.Rating 250kVA (See Section 4 ‘Technical Specifications’/ Part 2 ‘Information and documentation’ – Form 1 – ‘Schedule of Guaranteed Technical Particulars’)

1.8.4.Insulating oil i. filled with uninhibited transformer oil

1.8.5. ii.to IEC60296

1.8.6.Type of cooling:ONAN

1.9.Rated Voltages

1.9.1.HV11kV

1.9.2.LV ( On normal tap and no load ) Single voltage: 400V (See Section 4 ‘Technical Specifications’/ Part 2 ‘Information and documentation’ – Form 1 – ‘Schedule of Guaranteed Technical Particulars)

1.10. Tap changer

1.10.1.Type Off-circuit

1.10.2.Tapping range +5%, –5%

1.10.3.Tapping step2.5%

1.11. System highest voltage

1.11.1.HV12kV

1.11.2.LV 1.1kV

1.12. System earthing

1.12.1.HVResistance

1.12.2.LV Solid

1.13. Insulation level for HV winding

1.13.1.Rated short duration power frequency withstand 28kV r.m.s

1.13.2.Rated lightning impulse withstand voltage 75kV peak

1.14. Insulation level for LV winding

1.14.1.Rated short duration power frequency withstand 3kV

1.15. Connection symbol Dyn11

1.16. Impedance Voltage at principal tap and winding temperature of 75°C

1.16.1.250kVA (applies for this tender) 3.75 to 4.25%

1.16.2.500kVA (not applicable for this tender)3.75 to 4.25 %

1.16.3.800kVA (not applicable for this tender)4.25 to 4.75%

1.16.4.1000kVA (not applicable for this tender)4.75 to 5.25%

1.16.5.1600kVA (not applicable for this tender)6.00 to 6.50 %

1.17. Maximum sound pressure level Lp at 0.3 m 55dB(A)

1.18. Maximum overall dimensions

1.18.1.Width1200mm

1.18.2.Height 1400mm

2.Windings

2.1.The primary and secondary windings must consist of high conductivity copper wound on formers to produce coils.

2.2.[Aluminium windings, if offered, shall be deemed NOT Compliant]

2.3.For the purpose of voltage control, tappings must be provided on the higher voltage windings of all the transformers to give a transformation variation range of plus 5% and minus 5% in 2.5% steps.

2.4.i. The off-circuit tap selector switches must be operated by hand wheel external to and on one side of the transformer tank.