Sectionalizer, Auto Circuit Breaker, Distribution manufacturer / supplier in China, offering 15kv/27kv/38kv Recloser Wtith IEC61850 and DNP3.0 for Distribution and Substation, Pasgt Tactical M88 U. S. Army Steel Replica Anti-Riot Helmet Full Head Coverage with Adjustable Chin Strap for Personal Safety of Airsoft Hunting Paint Ball Bb, Od8mm Stainless Steel Bowfishing Line Guiding Rod with Ceramic Eyelet Accessory Fit Reel Seat Mount for Fishing Bow Fishing Slingshot and so on.

1
    YRS
General Supplier

China 15kv 24kv 38kv Outdoor Epoxy Resin Current Transformer

Get Latest Price
Min. Order / Reference FOB Price
10 Piece US $500.00/ Piece
Local Area: Ningbo, Zhejiang, China
R&D Capacity: OEM, ODM, Other
Payment Terms: LC, T/T, PayPal
Application: Instrument
Type: Current Transformer
Phase: Single

24kV CURRENT TRANSFORMERS FOR POLLUTED AREAS

No.RequiredOffered To be specifiedHEMG To be specifiedChina Manufacturer's reference/cat. NumberTo be specifiedLZW-24 Standards of quality managementISO 9001ISO 9001
(check attachment) Applicable standardsIEC 60185, IEC 60044-1 or equivalentIEC 60185, IEC 60044-1 or equivalent TypeSingle phase, outdoor, epoxy cast resin or polymer (silicone rubber or silicone alloy) insulator capable of operating under polluted conditions such as coastal areas, hoarfrost, industrial contamination, UV radiation, etc., as well as humid tropical climatSingle phase, outdoor, epoxy cast resin ,
insulator capable of operating under polluted conditions such as coastal areas, hoarfrost, industrial contamination, UV radiation, etc., as well as humid tropical climate Rated maximum system voltage [kV]2424 Ratio transformers (Double-ratio: Ir11-Ir12/Ir2) [A]
5-10/5
10-20/5
15-30/5
20-40/5
25-50/5
30-60/5
50-100/5
75-150/5
100-200/5
150-300/5
200-400/5
250-500/5
300-600/5
400-800/55-10/5
10-20/5
15-30/5
20-40/5
25-50/5
30-60/5
50-100/5
75-150/5
100-200/5
150-300/5
200-400/5
250-500/5
300-600/5
400-800/5 Number of secondary winding11 Accuracy class0.50.5
11
Rated continuous thermal current
1.2x(Ir11-Ir12)
1.2x(Ir11-Ir12) Rated burden [VA]1010 Rated short-time thermal current (Ith), 1s [kA]. CT 5-10/5A
CT 10-20/5A
CT 15-30/5A
CT 20-40/5A
CT 25-50/5A
CT 30-60/5A
CT 50-100/5A
CT 75-150/5A
CT 100-200/5A
CT 150-300/5A
CT 200-400/5A
CT 250-500/5A
CT 300-600/5A
CT 400-800/5A0.8
1.6
2.4
3.2
4.0
4.8
8.0
12.0
16.0
24.0
25.0
25.0
25.0
25.00.8
1.6
2.4
3.2
4.0
4.8
8.0
12.0
16.0
24.0
25.0
25.0
25.0
25.0 Rated dynamic current (Idyn) [kA]2.5 x Ith2.5 x Ith Rated frequency [Hz]5050 Lightning impulse withstand voltage (1.2/50ms [kVp]125125 Power frequency withstand voltage on primary winding, 50Hz, 1min [kVrms]5050 Power frequency withstand voltage on secondary winding, 50Hz, 1min [kVrms]22 Creepage distance [mm]³ 600³ 600 Max. ambient temperature [°C]5050 Max. relative humidity [%]9090 Limits of temperature rise [°C]6060 Included accessories1) The MV terminals and connectors made of tinplated copper for aluminum/copper conductors up to 240sqmm.2).The secondary wiring cover made of aluminum, stainless steel or hot dip galvanized steel; The bolts of the cover having a provision for security sealing.
.
3).The base made of aluminum, stainless steel or hot dip galvanized steel.
4)Bolts, nuts, and washers made of hot dip galvanized steel or stainless steel.1). The MV terminals and connectors made of tin-plated copper for aluminum/copper conductors up to 240sqmm.
2).The secondary wiring cover made of pastic
3) The base made of steel
4)Bolts, nuts, and washers made of hot dip galvanized steel or stainless steel. Inspection and tests1) Type tests, which have been carried out by an independent testing laboratory on the similar products, shall be submitted with the tender as follows:Shorttime current test;Temperaturerise test;Lightning impulse test on primary winding;Wet test for outdoor type transformer;Determination of accuracy.
2) Routine tests, which shall be made by the manufacturer on each supplied individual product at the manufacturer's factory, shall be submitted to the Purchaser upon the goods to be delivered. These tests shall be carried out as follows:Verification of terminal markings;Powerfrequency withstand test on primary and secondary windings;Partial discharge measurement;Powerfrequency withstand test between sections;Interturn overvoltage test;Determination of accuracy.-
3) Acceptance tests (sample test), which have been carried out by an independent testing laboratory on supplied typical voltage transformer, including:Powerfrequency withstand tests on primary and secondary windings;Determination of accuracy1)We offer the similar type test report LCZ-35
( because 35KV is stardared voltage in our country ,this voltage adapt below 35kv current transformer )
2).when manufacturer finish the producing , manufacturer will offer for buyer3).when manufacturer finish the producing , manufacturer will offer for buyer
Catalogues/drawings Check attachment Certificate of pattern approvalReference lists as stipulated in the commercial requirements