Business Type:
Manufacturer/Factory
Establishment:
2012
R&D Capacity:
ODM, OEM, Other
OEM/ODM Service
Sample Available

Sectionalizer, Auto Circuit Breaker, Distribution manufacturer / supplier in China, offering 15kv/27kv/38kv Recloser Wtith IEC61850 and DNP3.0 for Distribution and Substation, Pasgt Tactical M88 U. S. Army Steel Replica Anti-Riot Helmet Full Head Coverage with Adjustable Chin Strap for Personal Safety of Airsoft Hunting Paint Ball Bb, Od8mm Stainless Steel Bowfishing Line Guiding Rod with Ceramic Eyelet Accessory Fit Reel Seat Mount for Fishing Bow Fishing Slingshot and so on.

1
    YRS
General Supplier
Supplier Homepage Electrical & Electronics Power Transmission & Transformer Transformer China 33kv 17steps 250A Auto Voltage Regulator for Power Distribution Transformer

China 33kv 17steps 250A Auto Voltage Regulator for Power Distribution Transformer

Get Latest Price
Min. Order / Reference FOB Price
10 Piece US $5000.00/ Piece
Local Area: Ningbo, Zhejiang, China
R&D Capacity: OEM, ODM, Other
Payment Terms: LC, T/T, PayPal
Application: Power
Phase: Three
Certification: ISO9001-2000, ISO9001
33KV 250A 50HZ/60HZ AUTO VOLTAGE REGULATOR FOR POWER AND DISTRIBUTION TRANSFORMER


Technical Specification
SYTZZ-33/200-17 is designed and produced according to IEC-60214-1(2003), the main specifications is shown by Table 1.
Table 1 SYTZZ-33/200-17 series OLTC Technical Specification

ModelSYTZZ-33/200-17 max. through current240Phase number3Wiring methodEnd part voltage regulationMax working position number17Rated grade voltage600Insulation
Level
(KA)Insulation grade33Max working voltage36Industrial
test voltage 1minTo earth85Between phase85Between max. and min.36Between neighboring contact36Shocking test (1.2/50us)200Shout circuit testThermal stability(3S)4Dynamic stability10Mechanical life(10000 times)Not less than 50Electrical lifeNot less than 5Tight testWorking pressure3x104 PaTest pressure6x104 Pa 24h without leakageSwitch weight (without oil)(kg)130Oil weight filledAccording to switch heightDrying105+ 5ºCController fittedYK-2


4. The wiring diagram
(a ) (b)

SYTZZ-33/200-17
5. Operation Condition
5.1 Service ambient air temperature range of tap changer is -25ºC ~ +40ºC,Relative humidity is less then 85%.
5.2 Service temperature range of the tap changer in oil is -25ºC ~ +100ºC.
5.3 Vertical inclination of OLTC should not be over 2% when it is mounted onto the transformer.
5.4 OLTC should be operated in the place without heavy dusty and any corrosive or explosive gas.
6. Automatic Voltage Regulator
SYTZZ-33/200-17 OLTC is equipped with automatic voltage regulator YK-2. please refer to appendix for YK-2 automatic voltage regulator circuit diagram.
7. Special Design.
Special design will be provided according to the requirements of the customer. The OLTC can be equipped with temperature sensor for cold region application and a manual operation mechanism with DC power supply to YK-2 AVR for position display during installation.