Sectionalizer, Auto Circuit Breaker, Distribution manufacturer / supplier in China, offering 15kv/27kv/38kv Recloser Wtith IEC61850 and DNP3.0 for Distribution and Substation, Pasgt Tactical M88 U. S. Army Steel Replica Anti-Riot Helmet Full Head Coverage with Adjustable Chin Strap for Personal Safety of Airsoft Hunting Paint Ball Bb, Od8mm Stainless Steel Bowfishing Line Guiding Rod with Ceramic Eyelet Accessory Fit Reel Seat Mount for Fishing Bow Fishing Slingshot and so on.

1
    YRS
General Supplier
Supplier Homepage Electrical & Electronics Power Transmission & Transformer Instrument Transformer China 34.5kv 60Hz Epoxy Resin Outdoor Pole Mounted Combined CT PT Transformer

China 34.5kv 60Hz Epoxy Resin Outdoor Pole Mounted Combined CT PT Transformer

Get Latest Price
Min. Order / Reference FOB Price
10 Piece US $1000.00/ Piece
Local Area: Ningbo, Zhejiang, China
R&D Capacity: OEM, ODM, Other
Payment Terms: LC, T/T, PayPal
Application: Instrument
Type: Combined Transformer
Phase: Three

SPECIFICATION OF 34.5KV COMBINED CT PT TRANSFORMERModel: CCPT-34.5 Standard:IEC 61869-1&2&3&4Instrument transformers, CFE VE100-29
3. Working Condition
3.1 The highest voltage for equipment / frequency:38kV/60Hz
3.2 Working Temperature:-40ºC~40ºC
3.3 Three phase,Outdoor
3.4 Creepage distances: ≥28mm/Kv
3.5 Wind Speed:160KM/H
3.6 Sea Level: ≥2500m
4. Application
Applicable to the frequency of 60Hz, the highest voltage of 38kV, which is used for measurement and protection. Suitable for pole-mounted, outdoor
5. Main technical requirements
5.1 Wiring Connecting Diagram
5.2 Parameter sheet
5.2.1 Data of voltage transformerRated primary voltage (V)Rated primary voltage(V)AccuracyRated Burden(VA)Voltage factorVAth(VA)Rated insulation level(kV)201251150.2501.2Un/continue
1.9Un/8h50038/70/170 kV
Ext.BIL:200kV5.2.2 Data of current transformerRated
ratioRated load
(VA)AccuracyIcthIth(kA/1s)Idyn(kA)Rated insulation level(kV)10/5A,50/5A
200/5A150.2S200%80xIpr2.5xIth38/70/170 kV
Ext.BIL:200kV5.3 Withstand requirement: (installation site should be not more than 1000m under standard pressure )
5.3.1 Inductive withstand voltage: Pri.-Sec. &Ground 70kV/40s@180Hz,
5.3.2 Power frequency withstand voltage: Sec.-Sec. &Ground 3kV/1min, N earth terminal - Sec. &Ground: 3kV/1min
5.4 Insulation resistance test
Pri.-Sec. &Ground: ≥1000MΩ/DC2500V, Sec.-Sec. &Ground: ≥500MΩ/DC2500V
5.5 Partial discharge: meet standard IEC61869-1:2007
6.Dimension
Fig.1 Outline dimension