38KV SINGLE PHASE OUTDOOR EPOXY RESIN CASTING CURRENT TRANSFORMER FOR POLE MOUNTED
33KV outdoor type single phase CTSL
no.DescriptionUnitRequirementManufacturer's
guaranteedparticulars1Manufacturer's Name&country of origin To be mentionedHEMG2Manufacturer's model no To be mentionedLZW-35W23Application Metering and protection 4Type InductionInduction5Installation OutdoorOutdoor6Construction CASTINGCASTING 7insulation EPOXY EPOXY RESIN8Number of phases SingleSingle9Rated frequencyHZ50/6050/6010Mounting On supporting structure 11Primary rated voltage(phase to phase)kV333312Maximum system voltage
tease to(phase to phase)kV363613System earthing Effectively earthedEffectively earthed14Basic insulation level (1.2/50 Micro-sec)kV17017015Power frequency withstand voltagekV707016Ratio For 33/11KV 10/3.33 MVA Power Transformer Incoming and 33 kV outgoing feeder 400-200/5/5A400-200/5/5A For 33 kV Line feeder incoming 800-400/5/5A800-400/5/5A17Type of winding a)Primary Single WindingSingle Winding b)Secondary Double windingDouble winding18Accuracy class
a)for measurement
b)for protection 0.5
5P100.5
5P1019Burden
a)for measurement
b)for protectionVA
VA30
3030
3020Short time current rating for 3 secKA252521Extended current Rating(% of rated current)%12012022Over current RatingA101023Creepage Distancemm/kV(Min)252524Rated accuracy limit factor To be mentioned1025Knee Point VoltageVTo be mentioned/26Bushing outdoor typeoutdoor type27Standard As per relevant IEC-185Iec60044-1