Sectionalizer, Auto Circuit Breaker, Distribution manufacturer / supplier in China, offering 15kv/27kv/38kv Recloser Wtith IEC61850 and DNP3.0 for Distribution and Substation, Pasgt Tactical M88 U. S. Army Steel Replica Anti-Riot Helmet Full Head Coverage with Adjustable Chin Strap for Personal Safety of Airsoft Hunting Paint Ball Bb, Od8mm Stainless Steel Bowfishing Line Guiding Rod with Ceramic Eyelet Accessory Fit Reel Seat Mount for Fishing Bow Fishing Slingshot and so on.

1
    YRS
General Supplier

China 420kv 330kv 300kv Outdoor Disconnector

Get Latest Price
Min. Order / Reference FOB Price
1 Piece US $30000.00/ Piece
Local Area: Ningbo, Zhejiang, China
R&D Capacity: OEM, ODM, Other
Payment Terms: LC, T/T, PayPal
Type: High-voltage
Structure: Double-column Disconnector
Installation: Outdoor High-voltage


TECHNICAL DATA SCHEDULE
DISConNECT SWITCH 362 kV, 40 kA, 2000 A WITH GROUNDING BLADE
ITEM DEscriptION UNITS REQUIRED GUARANTEED
1.0 Manufacturer - HEMG
1.1vertical break vertical break
1.2 Model no - - GW-363
1.3 Country of origin - - China
2.0 Nominal characteristics
2.1 Rated System voltage KV 330 330
2.2 Rated maximum voltage kV 362 363
2.3 Lightning impulse withstand voltage kV peak 1175 1175
2.4 Switching impulse withstand voltage wet kV peak 950 950
2.5 Power frequency withstand voltage kV RMS 510 510
2.6 Rated frequency Hz 50 50
2.7 Number of poles - 3 3
2.8 Rated current A 2000 2000
2.9 Short time current withstand ability
during kA
s 40
3 40
3
2.10 Creepage distance to earth mm/kV 31
2.11 Opening time s < 30 9±2
2.12 Closing time s < 30 9±2
2.13 Max level of RIV (IEC 694) at 0,5 MHz and 362 kV test voltage V 2500 2500
2.14 Insulator designation (IEC 273) - - As per IEC
2.15 Grounding switch rated inductive (electromagnetic) breaking current breaking voltage A
kV -
- 1
2.16 Grounding switch rated capacitive (electrostatic) breaking current breaking voltage A
kV -
- 2
3.0 Operating mechanism motor and manual motor and manual
3.1 Motor voltage V dc 110 220
3.2 Number of auxiliary contacts available - min. 8 NO, 8 NC min. 8 NO, 8 NC
3.3 Number of mechanism - - 3
3.4 Main disconnector operated by - wheel or crank Crank
4.0 Weight and dimensions
4.1 Distance between poles mm - 5000~6000
4.2 Height of a pole mm - 10365±30
4.3 Height of the support structure mm 2500 2500
4.4 Total height mm - See drawing
4.5 Length of a pole mm - See drawing
4.6 Weight of a pole kg - 1000
4.7 Weight of the motor mechanism kg - 100
5.0 Accessories
5.1 Local/remote selector switch - Yes Yes
5.2 Local manual and electrical operation devices - Yes Yes
5.3 Light, heater and service plug in operating mechanism enclosure - Yes Yes
5.4 MCB protected motor and control circuits - Yes Yes
5.5 Motor contactor - Yes Yes
5.6 Test switches (dc) - Yes Yes
5.7 Terminal blocks - Yes Yes
5.8 Weatherproof corrosion resistant enclosure - IP 55 IP 55
5.9 Mechanical interlocks between the disconnect switch and ground blade - Yes Yes
5.10 Mounting brackets and hardware - Yes Yes
5.11 Arcing horns - For grounding blade For grounding blade

6.0 Grounding blades
6.1 Operated by wheel or torsion bar Crank
6.2 Mounting brackets and hardware yes yes
6.3 Number of auxiliary contacts available - 8 NO, 8 NC 8 NO, 8 NC
7.0 Type test reports number - To be included in bid Yes
10.0 Installation - Outdoor, desertic/tropical environment Outdoor, desertic/tropical environment

TECHNICAL DATA SCHEDULE

GROUNDING SWITCH 362 kV, 40 kA

CODE NO: 4115

ITEM

DEscriptION

UNITS

REQUIRED

GUARANTEED

1.0

-

-

HEMG

1.1

Type

-

vertical break

vertical break

1.2

Model no

-

-

JW-363

1.3

Country of origin

-

-

China

2.0

2.1

Rated System voltage

KV

330

330

22

Rated maximum voltage

kV

362

363

2.3

Lightning impulse withstand voltage

kV peak

1175

1175

2.4

Switching impulse withstand voltage

kV peak

950

950

2.5

Power frequency withstand voltage

kV RMS

450

510

2.6

Rated frequency

Hz

50

50

2.7

Number of poles

-

3

3

2.8

Rated current

A

N/A

2000

2.9

Short time current withstand ability
during

kA
s

40
3

40
3

2.10

Creepage distance to earth

mm/kV

31

31

2.11

Opening time

s

N/A

9

2.12

Closing time

s

N/A

9

2.13

Max level of RIV (IEC 694) at 0,5 MHz and 362 kV test voltage

mV

2500

2500

2.14

Insulator designation (IEC 273)

-

-

-

2.15

Grounding switch rated inductive (electromagnetic) breaking current at 10 kV breaking voltage

A

N/A

N/A

2.16

Grounding switch rated capacitive (electrostatic) breaking current at 16 kV breaking voltage

A

N/A

N/A

3.0

3.1

Motor voltage

Vdc

N/A

AC380

3.2

Number of auxiliary contacts available

-

N/A

N/A

3.3

Number of mechanism

-

N/A

N/A

4.0

4.1

Distance between poles

mm

-

See drawing

4.2

Height of a pole

mm

-

See drawing

4.3

Height of the support structure

mm

2500

2500

4.4

Total height

mm

-

See drawing

4.5

Length of a pole

mm

-

See drawing

4.6

Weight of a pole

kg

-

300

4.7

Weight of the hand mechanism

kg

-

100

5.0

5.1

Local/remote selector switch

-

N/A

N/A

5.2

Local manual and electrical operation devices

-

N/A

N/A

5.3

Light, heater and service outlet in hand operated mechanism enclosure

-

N/A

N/A

5.4

MCB protected motor and control circuits

-

N/A

N/A

5.5

Motor contactor

-

N/A

N/A

5.6

Test switches (dc)

-

-

Yes

5.7

Terminal blocks

-

yes

Yes

5.8

Weatherproof corrosion resistant enclosure

-

IP 65

IP 65

5.9

Mounting brackets and hardware

-

yes

Yes

5.10

Arcing horns

-

yes

Yes

6.0

-

-

6.1

Operated by

Wheel or torsion bar

orsion bar

6.2

Number of auxiliary contacts available

-

8 NO, 8 NC

8 NO, 8 NC

7.0

-

to be included in bid

Yes

8.0

-

Outdoor, desertic/tropical environment

Outdoor, desertic/tropical environment

TECHNICAL DATA SCHEDULE

DISConNECT SWITCH 362 kV, 40 kA, 2000 A WITH GROUNDING BLADES

CODE NO: 4114

ITEM

DEscriptION

UNITS

REQUIRED

GUARANTEED

1.0

-

-

HEMG

1.1

Type

-

vertical break

vertical break

1.2

Model no

-

-

GW-363

1.3

Country of origin

-

-

China

2.0

2.1

Rated System voltage

KV

330

330

2.2

Rated maximum voltage

kV

362

363

2.3

Lightning impulse withstand voltage

kV peak

1175

1175

2.4

Switching impulse withstand voltage wet

kV peak

950

950

2.5

Power frequency withstand voltage

kV RMS

510

510

2.6

Rated frequency

Hz

50

50

2.7

Number of poles

-

3

3

2.8

Rated current

A

2000

2000

2.9

Short time current withstand ability
during

kA
s

40
3

40
3

2.10

Creepage distance to earth

mm/kV

31

2.11

Opening time

s

< 30

9±2

2.12

Closing time

s

< 30

9±2

2.13

Max level of RIV (IEC 694) at 0,5 MHz and 362 kV test voltage

mV

2500

2500

2.14

Insulator designation (IEC 273)

-

-

As per IEC

2.15

Grounding switch rated inductive (electromagnetic) breaking current breaking voltage

A
kV

-
-

1

2.16

Grounding switch rated capacitive (electrostatic) breaking current breaking voltage

A

kV

-

-

2

3.0

motor and manual

motor and manual

3.1

Motor voltage

V dc

110

220

3.2

Number of auxiliary contacts available

-

min. 8 NO, 8 NC

min. 8 NO, 8 NC

3.3

Number of mechanism

-

-

3

3.4

Main disconnector operated by

-

wheel or crank

Crank

4.0

4.1

Distance between poles

mm

-

5000~6000

4.2

Height of a pole

mm

-

10365±30

4.3

Height of the support structure

mm

2500

2500

4.4

Total height

mm

-

See drawing

4.5

Length of a pole

mm

-

See drawing

4.6

Weight of a pole

kg

-

1000

4.7

Weight of the motor mechanism

kg

-

100

5.0

5.1

Local/remote selector switch

-

Yes

Yes

5.2

Local manual and electrical operation devices

-

Yes

Yes

5.3

Light, heater and service plug in operating mechanism enclosure

-

Yes

Yes

5.4

MCB protected motor and control circuits

-

Yes

Yes

5.5

Motor contactor

-

Yes

Yes

5.6

Test switches (dc)

-

Yes

Yes

5.7

Terminal blocks

-

Yes

Yes

5.8

Weatherproof corrosion resistant enclosure

-

IP 55

IP 55

5.9

Mechanical interlocks between the disconnect switch and ground blade

-

Yes

Yes

5.10

Mounting brackets and hardware

-

Yes

Yes

5.11

Arcing horns

-

For grounding blade

For grounding blade

6.0

6.1

Operated by

wheel or torsion bar

Crank

6.2

Mounting brackets and hardware

yes

yes

6.3

Number of auxiliary contacts available

-

8 NO, 8 NC

8 NO, 8 NC

7.0

-

To be included in bid

Yes

10.0

-

Outdoor, desertic/tropical environment

Outdoor, desertic/tropical environment