AC Contactor, Contactor, AC Contactor LC1-D manufacturer / supplier in China, offering Cjx2 (LC1) Excellent Quality AC Magnetic Contactor with Ce Certificate Motor Starter Relay Contactor, Knl1-63 (F360) Residual Current Circuit Breaker - 2007 Type, Miniature Circuit Breaker MCB with Ce CB S Knb6-63 (GRB60) 6ka- 10ka Sp Tp C6-25A C32~63A L7 Modification and so on.
Min. Order / Reference FOB Price | |
---|---|
1 Pieces | Contact Supplier |
Local Area: | Wenzhou, Zhejiang, China |
---|---|
R&D Capacity: | OEM, ODM, Other |
Payment Terms: | LC, T/T, PayPal |
Breaking Capacity: | Low Voltage Circuit Breakers |
---|---|
Operation: | Manual Type |
Speed: | Normal Type Circuit Breaker |
Sphere of application Model and meaning
Basic specification and main parameters Dimensions(mm)
The over-current tripping unit protection featureCharacteristics curve
Technique parameter:
Sphere of application
KNB6 High-breaking Miniature Circuit Breaker is nice in appearance, reasonable in structure, sound in feature and high in breaking capacity. Installed with standard din rail, it is convenient and easy in usage. It is mainly used in the line of AC 50/60Hz, rated working voltage to 415V, and rated current to 63A as protection against overload and short-circuit. It can be used as infrequent on-and-off operation and changeover.
It complies with standard of GB10963 and IEC/EN60898.
Basic specification and main parameters
frame class
63A
Rated working voltage240V/415V
Rated frequency50/60Hz
Rated working current6,10,16,20,25,32,40,50,63A
Making and breaking capacity10000A
Release typeC
Poles1,2,3,4P
Mechanical life10000
Electric life4000
The over-current tripping unit protection feature
Sequence
NO .
Release
Test
current I/In
Start state
Tripping
time
Expected
restlt
1
c
1.13In
Cold state
t≤1h
Not tripping
2
c
1.45In
Start right after
the serial NO .
1 test
t<1h
Tripping
3
c
2.55In
Cold state
1s
Tripping
4
c
5In
Cold state
t≤0.1s
Not tripping
5
c
10In
Cold state
t<0.1s
Tripping
Model and meaning
Dimensions(mm)
Characteristics curve