Sectionalizer, Auto Circuit Breaker, Distribution manufacturer / supplier in China, offering 15kv/27kv/38kv Recloser Wtith IEC61850 and DNP3.0 for Distribution and Substation, Pasgt Tactical M88 U. S. Army Steel Replica Anti-Riot Helmet Full Head Coverage with Adjustable Chin Strap for Personal Safety of Airsoft Hunting Paint Ball Bb, Od8mm Stainless Steel Bowfishing Line Guiding Rod with Ceramic Eyelet Accessory Fit Reel Seat Mount for Fishing Bow Fishing Slingshot and so on.

1
    YRS
General Supplier
Supplier Homepage Electrical & Electronics Breaker & Protector Circuit Breaker China Chz4 38kv 630A 800A 60Hz 50Hz 12.5ka 20ka Recloser for Substation Mounted Pole Mounted

China Chz4 38kv 630A 800A 60Hz 50Hz 12.5ka 20ka Recloser for Substation Mounted Pole Mounted

Get Latest Price
Min. Order / Reference FOB Price
1 Piece US $80000.00/ Piece
Local Area: Ningbo, Zhejiang, China
R&D Capacity: OEM, ODM, Other
Payment Terms: LC, T/T, PayPal
Breaking Capacity: High Voltage Circuit Breakers
Operation: Electric Type
Speed: High-Speed Circuit Breaker


1 APPLICATION :This manual is only applicate for the installation, operation and maintenance of CHZ4(ZW32)-33/630-12.5 automatic circuit recloser including Recloser Control.1.1 Note:Please read and understand carefully all the contents of this operation manual.
The operation manual is not possible to include all details of the automatic circuit recloser of CHZ4(ZW32)-33/630-12.5 if you need more detailed information, please contact us freely Mobile Number:0086+13805895904,Tel/Fax:0086-88079260.1.2 Warning:Don't operate the equipment just by following the instructions of operation manual,it is necessary to train operator to understand the operation manual before operator install ,operate and maintain the automatic circuit recloser.1.3 Operator's capacityThe buyer have the duty to confirm the capacity of operator who can install, operate and maintain the CHZ4(ZW32)-33/630-12.5 automatic circuit recloser including of :
Familiar with all the content of the manual
Trained of safety operation programs and technology of mid&low-voltage equipments.
Trained of operation programs of on-off electricity and authorized by General Manager.
Trained of operating mid&low-voltage protection equipment.2 Product name CHZ4(ZW32)-33/630-12.5 HV.AC outdoor automatic circuit recloser is combined of ZW32-33 vacuum circuit breaker and CHK4 Recloser Control.2.1 Product model CHZ4(ZW32)-33A/630-12.5KA
CHZ:AUTOMATIC CIRCUIT RECLOSER
4 : DESIGN SERIAL NUMBER
33 : RATED VOLTAGE KV
A:AUTOMATIC
630: RATED CURRENT A
12.5KA: RATED SYMETRIC SHORT CIRCUIT KA2.2 StandardANSI/IEEE C-37.60 IEEE Standard Requirements for Overhead,Pad-Mounted, Dry Vault, and SubmersibleAutomatic Circuit Reclosers and FaultInterrupters for Alternating CurrentSystems Up to 38 kV
ANSI/IEEE C-37.90 Relays and relay systems associated with electric power apparatus
IEC56-427HV.AC circuit breaker
GB1984-2003 HV.AC cirucit breaker
GB/T11022-1999 Common technology of HV.AC switchgear and Recloser Control equipments
DL/T403-2000Order technology conditions of 12-40.5kV HV.AC circuit breaker
Q/TG35-JTTechnology conditions of ZW32-33KV HV-AC outdoor vacuum circuit breaker2.3 Environment conditionsAltitude≤3500MASL
Ambient temperature is -45ºC-65ºC,the daily temperature difference is 25ºC
Wind speed is not more than 35m/s
Earthquake strength is not more than 8 degree
Pollution class:4 class
The installation site is free from explosion,fire and chemical corrosion 3 Technology Parameter of Vacuum circuit breaker3.1 Main technology parameter see talbe 1.talbe 1:Main technology parameter

SNOITMUNIT VAULUE33kV1Rated voltagekV332Rated FrequencyHz603Rated currentA630 4Rated short circuit currentkA12.55Rated peak withstand currentkA506Duration of rated short circuit currentkA/S20/47Rated short circuit making current (peak)kA508Rated operation sequencetimes0-0.2s-C0-2s-CO-2s-CO-30s9Mechanical lifetimes1000010Breaking times at rated short circuit currenttimes5011Power frequency withstand voltage in 1 minPhase to earth/phase to phase /breakkV7012Lightning impulse withstand voltage(peak) phase to earth/phase to phase /breakkV17013Secondary withstand voltage
in 1 minV2000

3.2 Magnetic mechanism parameter see table 2Tabl 2:Magnetic mechanism parameter

Name Value NoteModel YCK-CB Input voltage AC 220 UPS backup powerDC24 TypeSingle capacity coils and single stabilityDC220/110V
/24VCapacitor voltageDC75~DC300Optional Max coils current 80A~150A Max holding power5000N Max travel30mm Set max time of CO coils impulse current80msAutomatic adjustableEnvironment temperature-25to70ºCStandard-40to80ºCSpecial Fault counter1~3 times Operation counter0~9999

4 Vacuum circuit structure4.1 General ZW32 is a three-phase structure, each phase is combined of vacuum interrupter and operation insulator in the sealed pole. The permanent magnet mechanism adopts three-phase linkage, mounted in a sealed stainless-steel shell. Enclosure is with IP65. There are breather with prevent condensation unit at the bottom of the shell.
The magnetic mechanism is with interlock function to keep the operation of mechanism in good condition and keep the ON/OFF condition by electromagnetic lock. Tripping is done by a anti power of coils from a anti current .The operation power is supplied by the capacitor in the Recloser Control.
CHZ4(ZW32)-33/630-12.5 Automatic circuit recloser is with manual tripping function to keep the automatic circuit recloser at ON/OFF positions by handle the handshank out of the shell which is with indication ON/OFF ,it is easy for operator to watch conditions from the ground., the automatic circuit recloser's ON/OFF can be inspected by state of auxiliary switch .by current transformer of which rate is 400/1a CT to meter current and protect the overcurrent .The main insulated pole is poly insulating material which is anti-ultraviolet rays. The silicon rubber tube of outlet is with high creep distance. The terminal kit is 70x40x8mm T2Y tinned copper kits to connect with connector and overhead line.4.2 Cross drawing
picture1:ZW32cross drawing4.3 Outside sizeZW32 As below

picture2:ZW32 outside drawing4.4Main insulated bushing
picture3:Main insulated bushing
Main insulated bushing is poly insulated pole with anti-ultraviolet rays, the silicon rubber tube is with creep distance more than 800mm,the diameter is 235mm.it is suitable for working environments where is very heavy polluted.
The terminals kits on the upper pole is with size 70mmx40mmx8mm t2y tinned copper terminal kits
The power side terminal kits is marked with A,B,C ,for it is operated by LV mechanism ,both side can be power side.4.5Current transformer The current metering is achieved by 3 pcs current transformers of which rate is 400:1 at side of insulated bushing side.the secondary current outlet is connected to the protect module of current transformer at terminal part of the mechanism shell and connect to the Recloser Control by control cable .

picture4:ZW32 current transformer4.6 Voltage sensorThe voltage metering is achieved by 3pcs voltage sensors of which rate is 7.96v/0.4-7v at the side of insulated bushing. The secondary voltage sensor terminal is connected to the protect module of voltage at the terminal part of the mechanism part and connect to the Recloser Control by a control cable .

picture5:voltage sensor4.7 Manual handle for ON/OFFThe manual handle is made of stainless with barking finish ,the color is green ,the power is 20kg to draw down the handle to open the recloser.
picture6:manual handle for ON/OFF4.8 Indication of position O/C
Picture7: Indication of position O/C
The yellow arrow to "0" indicate "OPEN", the yellow arrow to "C" indicate "CLOSE"
4.9 Integration socket with control cable CHK4 Recloser's control cable connect Recloser Control and vacuum circuit breaker by the integration socket which include CT signal,voltage sensor signal and all the signals of coils and auxiliary switch signals, the cable length is 8m.

Picture8:integration socket with control cable
5 Automatic Circuit Recloser5.1 General The CHK4 Recloser Control Instruction Manual describes common aspects of recloser control application and use. It includes the necessary information to install, set, test, and operate the relay and more detailed information about settings and commands.
The CHK4 contains many protection, automation, and control features. Figure 5.1 presents a simplified functional overview of the relay.

Figure 5.1: Functional Overview
Note: Function with the order may be different.5.2 Parameter5.2.1 Basic parameteroperate cycle : 0.2S-CO-5S-CO-5S-CO Frequency operation times per hour:100 timesThe max working temperature:+55ºC The min working temperature:-40ºCThe max humidity 98% without condenseMax altitude 4000mProtect class IP55Mechanical vibrate anti capacity: 4M4Withstand capacity at limited temperature +75ºC/-20ºCElectrical strength1min power frequency withstand voltage according to IEC60255-5: 2KVImpulse voltage according to IEC60255-5 @ 1.2μs/50μs/0.5j: 6KVThe insulated resistor at 1000VDC: ≥5MΩ(EMC)Electromagnetic compatibilityVoltage Short time breaking and changeable is according to IEC6100-4-11 Voltage changeable 15%, time 2-3s, interval 5-10sThe electrical speedy momentary impulse interfere is according to IEC6100-4-4Vibration wave Interfere is according to IEC61000-4-12 The inrush current interfere is according to IEC61000-4-5The power frequency magnetic interfere is according to IEC61000-4-8 The impulse magnetic field interfere is according to IEC61000-4-9Damping oscillating magnetic field immunity is according to IEC61000-4-10