CJX2(LC1-D) series AC contactor(simplified as contactor in the following) is suitable for using in the circuits up to the rated voltage 660V AC 50Hz or 60Hz, rated current 95A, for making breaking an frequent starting, controlling the AC motor. Combined with the auxiliary contact group, air delayer, machine interlcking device, it is combined into the delay contactor, mechanical interlocking contactor, dtar-delta starter, with the thermal relay, it is combined into the electromagnetic starter.
Type CJX2-F115CJX2-F150CJX2-F185CJX2-F225CJX2-F265CJX2-F330CJX2-F400CJX2-F500CJX2-F630Main circuit characteristic Poles 3P.4PRated operation voltage (Ue) V380 660 1000Rated insulation voltage (Ui) V1000Rated heating current (Ith) A200200275275315380450630800Rated operation current (Ie)AC-3 380VA115150185225265330400500630AC-3 660VA86108118137170235303353462AC-3 1000VA46517190112115200232331AC-4 380VA52607985105117138147188AC-4 660VA4961698298118135145170Max. power of 3 phase
motor controlled AC-3 220VkW3040556375100110147200AC-3 380VkW557590110132160200250335AC-3 660VkW80100110129160220280335450Electrical life AC-310000 t60503020AC-410000 t1.51.50.80.5Machinery life 10000 t600600500500Operation frequencyAC-3t/h600600300300AC-4t/h150150150150Matching fuse type RT16-160RT16-200RT16-250RT16-315RT16-400RT16-400RT16-500RT16-630RT16-800Matching thermal relay type LR9-F53LR9-F73Wiring capacity mm25050959515018530x5(2)40X5(2)50X5(2)Coil Control power voltage (Us)ACV48110220380440600Allowed control circuit voltageCloseV85%~110%UsOpen V20%~75%Us (AC)Coil powerCloseVA5508001200120012501650 KeepingVA455513202422 Loss powerW12---1618---2412141820Auxiliary ContactACV380Rated heating current (Ith)DCV220Rated control capacity AC-15VA360DC-13W33