Extinguishant Control System, Extinguish Fire System, Extinguish Control Panel manufacturer / supplier in China, offering Fire Fighting Fire Alarm System with Fire Extinguishant Control Panel, AC220V Combustible Gas Detector Gas Alarm for Home Kitchen Using, Standalone Town Gas Detector LPG Leakage Gas Alarm Coal Gas Leakage Detector and so on.

1
    YRS
General Supplier
Supplier Homepage Security & Protection Alarm & Security Systems Alarm Host China Fire Alarm Control Panel Fire Alarm System Smoke Alarm Panel

China Fire Alarm Control Panel Fire Alarm System Smoke Alarm Panel

Get Latest Price
Min. Order / Reference FOB Price
1 Pieces US $180.00/ Pieces
Local Area: Shenzhen, Guangdong, China
R&D Capacity: OEM, ODM, Other
Payment Terms: LC, T/T, PayPal
Type: Fire Alarm Host
Function: Networked
Usage: Fire, Smoke

The CK1000 is a 4-zone to 16-zone FACP (Fire Alarm Control Panel), which uses conventional input devices. The panel accepts water flow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other normally-open contact devices. Outputs include four Notification Appliance Circuits (NAC, SOUND1-4), three standard Form-Arelays (alarm, trouble and supervisory) and an EIA-485 port to interface with remote annunciators and optional remote relay modules. The FACP is field programmable via the panel keypad. It also supervises all wiring, AC voltage and battery level.This series of panels are basically the same in application and operation, their differences are shown in Table 1-1. CK1000 will be described as the example in the following sections.Table 1-1FACPNumber of Detection ZonesNumber of Sounder OutputsOutput Delay SettingsCK100441N/ACK100882N/ACK1016164N/A
1.1ProductFeatures
4,8,16 Class BInitiating DeviceCircuits (IDCs)✓ Allzonesacceptconventionaldetectors andanynormally open contact deviceFourClass B Notification Appliance Circuits (NACs)One Form-AAlarmRelayOne Form-ATroubleRelayOne Form-ASupervisory Relay3.0ampsof system power Max 20 conventional detectors in one zone.Auto/Manual mode setting enable walk test.Each Zone can be disabled,Sound output can be disabled.Manual active sound output enabled.Able to report short and broken circuit of detection zones.Designed with standby batteries and space provision for two sealed lead-acid batteries.Testing and disable functions1.2SpecificationsAC Power
AC90-270VAC, 50 Hz, 2.3 amps
Wire size: minimum #14 AWG (2.0 mm2) with 600V insulation
Battery (lead acid only)
Maximum Charging Circuit: Normal Flat Charge-27.6V @ 0.8 amp
Maximum Charger Capacity: 18 Amp Hour batter
Sound OutputDevice Circuits
General Alarm Zones 1 through 16
Operation: All zones Class B
Normal Operating Voltage: Nominal 24 VDC (ripple = 100 mV maximum)
Alarm Current: 15 mA threshold
Short Circuit Current: 42 mA maximum
Maximum Loop Resistance: 100 ohms
End-of-Line Resistor: 4.7K, ½ watt

Standby Current: 7.26 mA
Three RelaysOutput
Relay contact rating: 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30 VAC (resistive)
Nonresettable24 VDC Power
MaxiMachinery for Glass & Ceramics mum ripple voltage: 10 mVRMSOperating Voltagenominal 24 volts
THand Tools otal DC current available fromthis output isup to500 mA
Recommended maximumStandby current is150 mA
Input CircuitCrushing & Culling Machine s
Sixteeninput circuitsprovide configuration. Input circuits 1 through 16maybeused as standard fire alarm controlpanel zones.All sixteenInitiating Device Circuitsacceptnormally-open contact devices and two-wire smoke detectors.Output Circuits
• 24 Volt Resettable Power Output 1000 mA
• 24 Volt NonresettablePower Output 1000 mA
• 24 Volt BatteryCharger (up to 18 AH batteries)
• EIA-485Port(interfacestoAnnunciators,andGraphicAnnunciators and Remote Relay Module)Sound (Notification Appliance )Circuits
Four Notification ApplianceCircuits.Relays
Three dryrelaysfor system alarm,system troubleandsupervisoryareprovidedstandard. Contacts are rated 2.0 amps @ 30 VDC(resistive)and 2.0 amps@ 30 VAC (resistive).EIA-485 Port
EIA-485compatibleportsupportsupto10differentdeviceaddresseswhichcan consist of Remote Annunciators, Relay Modules, Annunciators or Graphic Annunciatorsor any combination of the four modules.Battery Charger
BatteryChargerwillchargeupto18AHbatteries. TheCK1000cabinetholdsamaximumof7AHbatteries. The external boxis required tohold 18 AH batteries. The charger is ratedfor 500 mA maximumcurrent.