Business Type:
Trading Company
Business Range:
3D Printer, 3D Printer Filament
Establishment:
2016
R&D Capacity:
ODM, OEM, Other
OEM/ODM Service
Sample Available

Emerson, Power, Module manufacturer / supplier in China, offering Emerson Rectifier Module 48V 5800W for Netsure801 R48-5800 R48-5800e, Digital Voltmeter LED Display Mini 2/3 Wires Voltage Meter Ammeter, High Accuracy Red/Green/Blue DC 0V-30V 0.36" Digital Voltmeter LED Display and so on.

1
    YRS
General Supplier
Supplier Homepage Computer Products Network Hardware & Parts Communication Module China Huawei AC DC-Output Switching Power Supply for Me60 Ne40 EPS200-4850A

China Huawei AC DC-Output Switching Power Supply for Me60 Ne40 EPS200-4850A

Get Latest Price
Min. Order / Reference FOB Price
1 Piece US $1500.00/ Piece
Local Area: Beijing, China
R&D Capacity: OEM, ODM, Other
Payment Terms: LC, T/T, PayPal
Usage: Workstation, Telecommunication
Type: Wireless
Support Network: Ethernet

EPS200-4850A AC power chassis AC-input and DC-output Switching Power Supply for ME60 NE40

The AC power system supports 200-240 V AC power. It supports 110 V dual-live-wire inputs but not 110 V AC single-phase inputs. If 110 V dual-live-wire inputs are used, the voltage must range from 180 V to 264 V.

AC power input is converted into regulated DC power by an AC/DC converter.

Table 1 Power attributes

Attribute

Description

Description

Power Distribution Cabinet,220V,50/60HZ,72000mA,EPS200-4850A

BOM

02400376

Model

CR5B0PWRBX60


Table 2 Mapping products and versions

Product

Earliest Software Version

NE40E-X8

V600R001

NE40E-X16

V600R001

AppearanceFigure 1 Appearance of the EPS200-4850A (front view)
Figure 2 Appearance of the EPS200-4850A (rear view)
PanelTable 3 Indicators

Indicator

Color

Normal Status

Abnormal Status

Reason

Operation indicator

Green

On

Off

Mains is faulty (no AC input, or overvoltage/undervoltage of the AC input), or the power module does not have AC output.

Protection indicator

Yellow

Off

On

A temperature alarm is generated. (If the temperature exceeds 65°C [149°F], the device will be powered off due to overtemperature.)

The device is in the dormant state (only the indicator is On and no alarm is generated).

Fault indicator

Red

Off

On

The device is powered off due to over-output-voltage or overtemperature, or fans are faulty, or the power module d

Technical Specifications

Item

Specification

Dimensions (H x W x D)

Power distribution cabinet: 86.1 mm x 442 mm x 580 mm (3.39 in. x 17.40 in. x 22.83 in.)

Power module: 89 mm x 103 mm x 243 mm (3.50 in. x 4.06 in x 9.57 in.)

Weight

EPS200-4850A: 10 kg (22.1 lb)

Power module: 2.8 kg (6.17 lb)

Number of AC power input channels

4

Rated AC input voltage

200 V AC to 240 V AC

AC input voltage range

180 V AC to 264 V AC

Maximum AC input current

16 A

Number of DC output channels

4

DC output voltage

53.5 VDC

Maximum DC output current

55 A/module

Typical power consumption

138 W/module

Typical heat dissipation

447.7 BTU/hour