Business Type:
Trading Company
Business Range:
Steam Boiler, Boiler, Oil Heaters, Boiler Accessories
Establishment:
2018
R&D Capacity:
OEM, ODM, Own Brand
OEM/ODM Service
Sample Available

Boiler, Hot Water Boiler, Vacuum Boiler manufacturer / supplier in China, offering Horizontal Vacuum Oil/Gas Fired Hot Water Boiler for Home Usage, 2ton Coal/Multi Fuel Fired Steam Boiler with Best Quality, Grate for Kinds of Boiler and Furnace and so on.

1
    YRS
General Supplier
Supplier Homepage Industrial Equipment & Components Boiler & Furnace Boiler China Industrial Packaged Coal Fired Travelling Grate Steam Boiler1-35tph

China Industrial Packaged Coal Fired Travelling Grate Steam Boiler1-35tph

Get Latest Price
Min. Order / Reference FOB Price
1 Piece US $5000.00/ Piece
Local Area: Beijing, China
R&D Capacity: OEM, ODM, Other
Payment Terms: LC, T/T, PayPal
Function: Water Boiler, Steam Boilers
Fuel: Coal-Fired
Installation: Assembled Boiler

This is a coal-fired horizontal double-drum steam boiler. Simply, I consist of steam drum, water drum, convection tubes, insulation lay, steel coat, coal feeder, chain grate furnace and so on.
1. Boiler Features:
- After simplifying the water-cycle route, we can reduce the water-cycle resistance, raise ascending tube velocity, improve the stability of the water cycle and ensure a safe and stable operation.
- Design enough heating surface, which makes more heat from fuel absorbed. Flue smoke temperature can be lower than 170ºC.
- Reasonably design front and back arch to improve the temperature in the furnace. We also strengthen the disturbance of smoke in the high temperature area. These reduce heat lose and fly ash loss as a result of incomplete combustion.
- We adopt light chain grate and independent air chamber. We strengthen the seal airtight of the two sides of chain grates. These make the fuel burn fast and fully.
- Our boiler have a large convection heating surface, a stable performance and even a long time overload work. What's more, we design the convection tube bundles in alternate permutation instead of in-line arrangement. All of these designs make our boilers obtain a higher heat efficiency than normal, up to 81%.
- We design double side air inlet and independent air plenum. And at the exit of furnace, we set up a smoke separation device by inertia, which makes the original discharging dust concentration lower than 1800 mg/Nm3. Our high efficiency dust collector makes sure the dust removal efficiency up t0 90%, SOX and NOX removal efficiency up to 98%. These measures can meet the global demands and standards of environmental protection.
- Compact structures are designed, except the 4t/h and 6t/h packaged steam boiler. That can save boiler house and reduce the installation workload and time.
- We enlarge the diameter of steam drum to supply a big space of water-steam separation device. So that we can offer steam in good quality.
- High automatization, safe and easy operation. In the electrical control cabinet, we design automatic feeding water, alarm and safety interlock of high/low water level, air blower and draft fan.
2. Control and safety systems
The control and safety systems are interlocked in an electric control cabinet.
- Sound-light alarm of high and super-high steam pressure;
- Sound-light alarm of high and lowe water limit level;
- Sound-light alarm of pressure loss in the water pumps;
- More safety devices are designed and connected with the electric control cabinet (ECC). More details will be explained in the ECC Manual.
Boiler ModelSZL6-1.25/1.6/2.5-AIISZL8-1.25/1.6/2.5-AIISZL10-1.25/1.6/2.5-AIISZL20-1.25/1.6/2.5-AIISZL25-1.25/1.6/2.5-AII Rated Evaporation Capacityt/h6810152025Operation PressureMpa1.25/1.6/2.51.25/1.6/2.51.25/1.6/2.5 1.25/1.6/2.51.25/1.6/2.51.25/1.6/2.51.25/1.6/2.5Steam TemperatureºC194//204/226194//204/226194//204/226 194//204/226194//204/226194//204/226194//204/226Water-inlet TemperatureºC202020 20105105105 Heating Efficiency%≥78≥78≥80 ≥80≥81≥81≥81Area of Boiler Heating Surfacem3147.8175220 388443578626Area of Stokerm37.69.611.72 14.217.222.626.3Coal Available II type bitumite,low heat capability:17700-21000KJ/kgWater PumpModel 2GC-5x62½GC-6x6DG12-25x7 DG15-35x5DG15-35x5DG25-35x5DG46x30Motor PowerKW15/18.515/18.518.5/22 22/3022/3030/3737/45Blast FanModel G6-41-13
NO7.1AG6-41-13
NO8.5AG6-41-13
NO8.5A G6-41-13
NO8.5AG6-41-13
NO8.5AG6-73-11
NO11DG4-68-10DVentilationm3/h5349-103549369-181379369-18137 9369-181379369-181373610033173-
58856 Wind PressurePa1697-22702535-33912535-3391 2535-33912535-339127302313-3401 Motor PowerKW7.518.518.5 18.518.53745Induced Draft FanModel Y6-41-13
NO10CY6-41-13
NO11.2DY6-41-13
NO11.2D Y6-41-13
NO11.2DY8-39-13
NO10DGY20-15Y4-68
NO12.5DVentilationm3/h32144-
1660441773-
2157841773-
21578 41773-
2157845007330860611-
110772 Wind PressurePa2575-34442764-36972764-3697 2764-3697320535153765-2589Motor PowerKW374545 5590110132Dimensions of Biggest Parts for ShipmentM7.83x3.34x
3.468.82x3.34x
3.468.0x3.5x
2.7 7.2x3.3x
3.68.0x3.3x
3.610.6x3.35x3.6910.8x4.46x3.76Weight of Biggest Parts for ShipmentT48/51/5356/58/6096/97/98 102/103/104107/108/109152/154/156210/212/214