Business Type:
Manufacturer/Factory
Business Range:
MCCB, Contactor, Circuit Breaker
Establishment:
2007
R&D Capacity:
OwnBrand, ODM, OEM
Terms of Payment:
LC, T/T, PayPal, WesternUnion, Small-amountpayment
Main Markets:
Europe, Southeast Asia, Middle East, Australia
OEM/ODM Service
Sample Available

Automatic Transfer Switch, ATS, Change Over Switch manufacturer / supplier in China, offering PC Class ATS Change-Over Switch 16-3200A Automatic Transfer Switch for Generator, Sq5 Manual Changeover Switch ATS Electrical Changeover Switch, 20ka-40ka DC500V Solar DC Surge Protector and so on.

1
    YRS
General Supplier
Supplier Homepage Electrical & Electronics Breaker & Protector Circuit Breaker China Molded Case Circuit Breaker 400AMP MCCB 3 Pole

China Molded Case Circuit Breaker 400AMP MCCB 3 Pole

Get Latest Price
Min. Order / Reference FOB Price
1 Piece Contact Supplier
Local Area: Wenzhou, Zhejiang, China
R&D Capacity: OEM, ODM, Other
Payment Terms: LC, T/T, PayPal, WesternUnion, Small-amountpayment
Breaking Capacity: Low Voltage Circuit Breakers
Operation: Manual Type
Speed: Normal Type Circuit Breaker

Molded Case Circuit Breaker 400AMP MCCB 3 Pole
Keyword:1P,3P(3P+N),4Pole, Apply for isolator switch, Electric and thermal magnetic tripping device,

Provide miniature circuit breaker lockouts,Similar Tmax.

Application of (SM8max) MCCB

The SM8max T1 1p, T1, T2, T3, Ts3, T4, T5 and T6 circuit breakers can be fitted with thermal

magnetictrip units and are used in protection of alternating and direct current networks with a range of

use from15 A to 800 A. They allow the protection against overload with a thermal device (with fixed threshold

forT1 1p, T1, T2, T3, Ts3, T4 and adjustable threshold for T4, T5 and T6) realized using the bimetal technique,

and protection against short-circuit with a magnetic device (with fixed threshold for T1, T2, T3, Ts3

and T4 up to 50 A and adjustable threshold for T4, T5 and T6).

The four-pole circuit breakers are always supplied with the neutral protected by the trip unit

and with protection of the neutral at 100% of the phase settings up to 100 A. For higher settings,

the protection of the neutral is at 50% of the phase setting unless the protection of the neutral at 100% of

the phase setting is required.

Working conditions of MCCB

1. Not over altitude 2000m;

2. Ambient temperature is between-25°C and +40°C ; Working in the medium which not any explosive,

not enough dielectric to corrode metal, no gas to damage insulation and electric conduction dust;

3. Working in the place would not be invaded by rain and snow; 3. Pollution degree3; 4. Mounting type.

Classification of MCCB

1) According to using: distribution circuit protection type, motor production type;

2) According to connection mode: front panel connection, back panel connection, plug-in connection;

3) According to operating way: for direct handle operating, for motor operator operating, for rotary handle operating.

4) According to the number of pole: 3,4 pole.

5) According to the accessory: with accessory setting, and without accessory setting.


Rated current of release(A)

Thermodynamic release(ambient temp+40 )

Operation current
of magnetic release(A)

1.05ln(cold state)
inoperative time(h)

1.30ln(heat state)
inoperative time(h)

ln 63

1

1

10-50ln 20%

63 ln 250

2

2

10ln 20%

250 ln 800

2

2

5-10ln 20%



Rated current of release(A)

Thermodynamic release(ambient temp+40 )

Operation
current
of magnetic
release(A)

1.0ln(cold state)
inoperative
time(h)

1.20ln(heat state)
inoperative
time(h)

1.50ln(heat state)
inoperative
time(h)

1.0ln(heat state)
inoperative
time(h)

12.5 ln 400

2

2

4min

2S Tp 10S

12ln 20%


ABB Tmax (SM8max) MCCB SPECS

Type

T1-100

T1-160

T3-250

T5-400

T5-630

T6-800

Pole nunmber

1,3

3

3

3

3

3

Rated current ln(A)

25,32,40,50,
60,80, 100

125,160

160,200,250

300,400

500,630

700,800

Rated insulation voltage Ui(V)

AC500

AC660

AC660

AC660

AC660

AC660

Utilisation category

A

A

A

A

A

A

Rated ultimate short-circuit breaking capacity lcu(KA) at 415V

25

65

65

65

65

65

Rated short-circuit service breaking capacity lcs(%lcu)at 415V

75%

75%

75%

75%

75%

75%