Sectionalizer, Auto Circuit Breaker, Distribution manufacturer / supplier in China, offering 15kv/27kv/38kv Recloser Wtith IEC61850 and DNP3.0 for Distribution and Substation, Pasgt Tactical M88 U. S. Army Steel Replica Anti-Riot Helmet Full Head Coverage with Adjustable Chin Strap for Personal Safety of Airsoft Hunting Paint Ball Bb, Od8mm Stainless Steel Bowfishing Line Guiding Rod with Ceramic Eyelet Accessory Fit Reel Seat Mount for Fishing Bow Fishing Slingshot and so on.
Min. Order / Reference FOB Price | |
---|---|
1 Piece | US $30000.00/ Piece |
Local Area: | Ningbo, Zhejiang, China |
---|---|
R&D Capacity: | OEM, ODM, Other |
Payment Terms: | LC, T/T, PayPal |
Application: | Power |
---|---|
Phase: | Three |
Core: | Core-type Transformer |
THREE PHASE TRANSFORMER PEDESTAL TYPE 500 KVA, 10.5/0.23 KV
FOR WORKING IN ALTITUDE OF 3500 M.O.S.L.
Ítem
Descriptión
Unit
Required
Guaranteed
1
GENERAL DATA
1.1
Manufacturer
To indicate
HEMG
1.2
Country
To indicate
P.R.China
1.3
Brand
To indicate
HEMG
1.4
Power
KVA
500
500
1.5
Number of coils
2
2
1.6
Number of phases
3
3
1.7
Altitude of operation
3500
3500
1.8
Mounting
Outdoor
Outdoor
2
NOMINAL DATA AND CHARACTERISTICS
2.1
NominalFrequency
Hz
60
60
2.2
Nominal Voltage High voltaje side without load
KV
10.5+/-2x2.5%
10.5+/-2x2.5%
2.3
Nominal Voltage low voltage side without load
kV
0.230
0.230
2.4
Insulation level high voltage
Insulation Class
KV
12
12
Impulse Withstand Voltage 1.2/50 of external insulation
kVp
125
125
Impulse Withstand Voltage 1.2/50 of internal insulation
kVp
75
75
Withstand voltage industrial frequency
KV
28
28
Number of terminals in the primary side
6
6
Material of the coils
Copper
Copper
Bridge capacity for work in mesh or ring.
Amps
200
200
2.5
Insulation level low voltage side
Insulation Class
KV
1.1
1.1
Withstand voltage industrial frequency
KV
3.0
3.0
Material of the coils
Copper
Copper
Number of terminals in the secondary side
u
3
3
2.6
ConnectionGroup
Dyn5
Dyn5
2.7
Type of working
Meshor ring
Meshor ring
2.8
Shortcircuit voltage at 75 C
%
4
4
2.9
Losses
VA
30
30
Losses in the iron (% Nominal Power )
1179 w
1179 w
Losses in the copper with full load (% Nominal Power )
6540 w
6540 w
2.10
On temperature rise ( Limit Max Power onAN )
On temperature rise in the hot point of the coils
C
65
65
On temperature rise of the oil in the top side of the tank
C
60
60
2.11
Type of Oil
Mineral, free of PCBs
Mineral, free of PCBs
2.12
Standard for design, manufacture and test reports
Indicate
IEC60076
2.13
Standard for capacity of overload
Indicate
IEC60076
2.14
Standard for insulation oils
Indicate
IEC60296
2.15
Standard for the bushing plug type
Indicate
IEC60076
2.16
Standards for guaranteed losses
Indicate
IEC60076
3.0
Equipments
3.1
Cabin of Medium Voltage
Yes
Yes
Load Break switch submergible in oil, arranged such as to allow the primary network continue without interruption even when the transformer is out of service.
Yes
Yes
Hold fuse Bay -O-Net type
Yes
Yes
Fuses system Bay -O-Net current sensing
Yes
Yes
Current limiting fuses
Yes
Yes
Resyn insulators for system of connector plug-in
Yes
Yes
Lock of the door
Yes
Yes
Support of parking
Yes
Yes
Plugs connector for Medium Voltage cubit type
Yes
Yes
Kit of grounding of plugs connectors
Yes
Yes
3.2
Cabin of low voltage
Yes
Yes
Porcelain Insulators
Yes
Yes
General Circuit Breaker for low voltage
Yes
Yes
Auxiliar Circuit Breaker for low voltage
Yes
Yes
interlocking for the door
Yes
Yes
Lock of the door
3.3
Transformation Module
Yes
Yes
Indicator of oil level
Yes
Yes
Yes
Yes
Drain tap
Yes
Yes
Lifting ears
Yes
Yes
Nameplate
Yes
Yes
Vacuum tap changer
Yes
Yes
Terminal for grounding
Yes
Yes
Viwefinder of oil level
Yes
Yes
Well for measure temperatures
Yes
Yes
3.4
Telescopic pole operation of 6 bodies, 33 KV
yes
yes