AC Contactor, Contactor, AC Contactor LC1-D manufacturer / supplier in China, offering Cjx2 (LC1) Excellent Quality AC Magnetic Contactor with Ce Certificate Motor Starter Relay Contactor, Knl1-63 (F360) Residual Current Circuit Breaker - 2007 Type, Miniature Circuit Breaker MCB with Ce CB S Knb6-63 (GRB60) 6ka- 10ka Sp Tp C6-25A C32~63A L7 Modification and so on.
Min. Order / Reference FOB Price | |
---|---|
1 Pieces | Contact Supplier |
Local Area: | Wenzhou, Zhejiang, China |
---|---|
R&D Capacity: | OEM, ODM, Other |
Payment Terms: | LC, T/T, PayPal |
Breaking Capacity: | Low Voltage Circuit Breakers |
---|---|
Operation: | Manual Type |
Speed: | Normal Type Circuit Breaker |
Sphere of application
KNBL6-63 series leakage breaker is suitable for the leakage protection of the line of AC 50/60Hz, rated voltage single phase 240V, rated current up to 63A. When there is human electricity shock or if the leakage current of the line exceeds the prescribed value, it will automatically cut off the power within 0.1s to protect human safety and prevent the accident due to the current leakage.
KNBL6-63 series leakage breaker can protect against overload and short-circuit. It can be used to protect the line from being overloaded and short circuited as well as infre-quent changeover of the line in normal situation. It complies with standard of IEC/EN61009-1 and GB16917.1.
Basic specification and main parameters
frame class
63A
Rated working voltage
240V
Rated frequency
50/60Hz
Rated working current
6,10,16,20,25,32,40,50,63A
Rated residual operating current
0.01,0.03A
Rated residual un-operating current
0.005,0.015
Sensibility
AC Type
Maximum operating time
In t≤0.4s , 5In t≤0.01
Instant release type
B,C type
Limiting value of un-operating current
6In
Rated limiting short-circuit current
10000A
Pole number
1P+N
Mechanical life
4000
Electric life
80000
The over-current tripping unit protection feature
Sequence NO.
Release
Test
current I/In
Start state
Tripping
time
Expected
restlt
1
C
1.13In
Cold state
t≤1h
Not tripping
2
C
1.45In
Start right after
the serial NO .
1 test
t<1h
tripping
3
C
2.55In
Cold state
1s
tripping
4
C
5In
Cold state
t≤0.1s
Not tripping
5
C
10In
Cold state
t<0.1s
tripping