Business Type:
Manufacturer/Factory
Establishment:
2012
R&D Capacity:
ODM, OEM, Other
OEM/ODM Service
Sample Available

Current Transformer, Split Core Current Transformer, Split Current Transformer manufacturer / supplier in China, offering Waterproof Outdoor Split Core CT Current Transformer for Power Meter, 500/5A Split Core CT Current Transformer, 2500 AMP Accu CT Split Core Current Transformer 333mv Sensor and so on.

1
    YRS
General Supplier
Supplier Homepage Instruments & Meters Electronic Instrument Calibrator China Six Phase Current Injection Protection Relay Test Set

China Six Phase Current Injection Protection Relay Test Set

Get Latest Price
Min. Order / Reference FOB Price
1 Set US $35000.00/ Set
Local Area: Chaoyang, Liaoning, China
R&D Capacity: OEM, ODM, Other
Payment Terms: LC, T/T, PayPal
Application: Mechanical Instrument, Electromagnetic Instrument
Power: Electricity
Certification: FDA, CE, IAF, CCC
TEST-630 Six Phase Current Injection Protection Relay Test Set
Features
Integration in the host crystal 8.4 inches true color, light weight and easy to carry;
Built-in high-speed high-performance industrial computer, embedded operating system, running a stable and reliable; Also be connected PC testing;
Panel embedded user-friendly buttons can also be an external keyboard, mouse;
High-precision DAC to 12 Road, simultaneous output to ensure that waveform fitting of high precision, good linearity;
Matching electromagnetic compatibility components, can improve on-site anti-electromagnetic interference, protection devices can be connected electromagnetic compatibility tests;
Analog output of the front panel, switch the amount of terminal design in the upper cover, all the wiring does not affect the operation of the panels and test parameters of the surveillance;
Designed to the latest thermal structure, and to ensure the best ventilation. Automatically determine the over-current, over voltage, overload, short circuit, the temperature is too high, data anomalies and misuse warning prompt;
Using voltage, current amplifier AC / DC sharing, output stage uses a unique ultra-linear amplifier technology, high precision, good reliability; Six-phase AC output voltage and six-phase AC current;
12 analog ports, and the other optional auxiliary DC source output (220V/110V);
Interface: RJ45 (Ethernet interface), USB interface (software upgrades, reporting transmission), industrial serial interface (GPS or other serial device use).
Functions
Host real-time operating system, fast response, when faced with an emergency situation, to better protection of instruments and equipment under test. Safe and reliable, not easy to be a computer virus violated;
The newly designed software interface style, the host machine operation is fully consistent with the background and easy;
Extensive testing capabilities: The state sequence determined in the trial, IT features analog oscillation, the entire group of tests, differential protection, harmonic superposition, low cycle load shedding, same equipment, measuring instruments, GPS synchronized debugging, fault playback, and custom test (special tests), etc., to satisfy various types of user testing microprocessor-based protection relay needs. Can easily complete the Siemens, AREVA and other foreign manufacturers of protective device test.
The test report can be easily derived from the USB port to print.

AC current outputPhase current output (effective value) 6x0~30A or 3x0~60A
Maximum output power 520VA/phase
Maximum parallel current output (effective value) 0~180ALong-term allowable working value of phase current (effective value) >10A
Allowable working time of maximum current >11s
Accuracy<±0.2%AC voltage outputPhase voltage output (effective value) 6x0~130V
Line voltage output (effective value) 0~260VMaximum output power70VA/phase
Accuracy<±0.2%DC voltage outputOutput range0~300V or 6x0~±130V
Maximum output power130VA
Accuracy<±0.2%DC current outputOutput range -10~10A or 6x0~±10A
Maximum output power 150VA
Accuracy <±0.2%Binary inputIdle contact1~20mA, 24V (DC)
Electric potential contact0~250V (DC)Binary outputIdle contact 250V/0.5A (DC)Rated outputFrequency error <±0.01HzHz
Phase error <±0. 2°
Waveform distortion<±0.3% (fundamental wave)
Time error <40µs
Output frequency0~1050Hz
Superposed harmonic wave 0~21timesPower voltageAllowable range AC220V±10%, 50Hz±10%Ambient temperatureUse range 0~45
Storage range-25~70Time measurementTest range 0.1ms~999999.999sExterior appearance of cabinetimported electromagnetic compatible cabinet, which is made of high-grade all aluminum alloy extruded section and has fine appearance, is selected.
Dimension of cabinet: lengthxwidthxheight 360mmx195mm x365mmWeight of cabinetWeight of host machine 16.6kgLoad-bearing outputSelectable between light load or heavy load output
(When any phase current output surpasses 15A, it is suggested to press key F3 before test of each functional module so as to switch to heavy load output mode)