Business Type:
Manufacturer/Factory
Establishment:
2012
R&D Capacity:
ODM, OEM, Other
OEM/ODM Service
Sample Available

Current Transformer, Split Core Current Transformer, Split Current Transformer manufacturer / supplier in China, offering Waterproof Outdoor Split Core CT Current Transformer for Power Meter, 500/5A Split Core CT Current Transformer, 2500 AMP Accu CT Split Core Current Transformer 333mv Sensor and so on.

1
    YRS
General Supplier

China Three Phase Digital Electricity Power Meter

Get Latest Price
Min. Order / Reference FOB Price
3 Piece US $200.00/ Piece
Local Area: Chaoyang, Liaoning, China
R&D Capacity: OEM, ODM, Other
Payment Terms: LC, T/T, PayPal
Display: Digital
Usage: Multi-Functional Energy Meter, Watt-Hour Meter, Meter for Industry and Home Use, Reactive Energy Met
Electric Equipment: Three-phase Four-wire
FU2200 Multifunction Power Meter
Introduction
FU2200 is a power analyzer and meter, It can measure and display all the electrics parameters as well as harmonics content, Four modules can be plugged-in together: RS-485 communications, digital input/output, energy pulse, and DC 4~20mA analog output, So as to meet all kinds of demands.
Measurement Parameters
Voltage (pH-N); Voltage (pH-pH); Current; Frequency; PF; Active Power(W); Reactive Power(Q); Apparent Power(S), 3~19th harmonics
Harmonics
Total harmonics content of phase-voltage
Total harmonics content of current
3rd~19th harmonics content of Phase-Voltage (RS485 output)
3rd~19th harmonics content of current (RS485 output)
Maximum Value
Max. Value for voltage/current
Max. Value for active power
Max. Value for reative power
Max. Value for apparent power
Computation
Forward active power energy
Reverse active power energy
Forward active power energy
Reverse reactive power energy
Measuring Range
30~600V, 0~6A, 45~65Hz, -1~0~1
Measuring Accuracy
Frequency: 0.1%
Electric energy: 0.5%, 1.0%
Voltage: 0.2%± 0.1V
Current: 0.2%± 0.001A
Power: 0.5% ± 0.4W
Power Factor: 0.5% ± 0.001
Display
Wide screen angle, Light blue back-lit LCD Display, 5 Displays figures. 6 operation keys.
Communication
RS-485 interface port support, 32 (128) Networking, ModBus-RTU communication protocol.
Energy Pulse (Expansion)
FM-E2 provides active & reactive energy pulse output. Pulse parameters can be choose, range: 0.1~10000kWh/kvarh. Dry contact output (1A*100V).
Data Collection (Expansion)
Each FM-K2 module can be collected 2-ways of contacts and counting.
Control (Expansion module)
Each FM-K2 provides 2 relay outputs, which can be controlled by communication or the measured parameters.
Analog Output (Expansion module)
Each FM-A20 module provides 2 ways of DC 4~20mA output, It can be set the function-relations about parameters.
Connection Mode
3P4W, 3P4W BAL, 3P3W, 3P3W BAL, 1P2W, 1P3W.
Programmable
Measuring System: 3P4W/3P3W etc.
Transformation Ratio: PT, CT.
Communication
Address: 1~247; Baud: 1200~19200; Parity Bit: N/E/O
Energy: Reset
Dimension
Mounting Panel: 96 X 96mm
Thickness: 20mm
Depth: 60mm (without expansion module)
80mm (without expansion module)
Mounting
Panel Mounting
Trepanning: 92 X 92mm
Power Supply (AC/DC)
AC85~265V / DC85~330V, DC18~90V (optional)
Power Consumption: <4VA
Working condition
Temperature: -25 ~ 55 ° C
Humidity: 20% ~ 95%RH, Without condensation