Features:Touch panel and mask button, massive information to see and simple to usebuilt-in standard energy meter for digital closed loop feedback, U, I, Φ, F, W, VAR, VA, PF for referencePerfect over circuit, over voltage. short circuit, open circuit, over heat, over load protection Independent control on Three phase voltage current circuits, every phase U I can be regulated.Auto shift range, can freely preset rated value Multiple choose of voltage, current, phase regulation test point With R232 communication interface for PC control and software upgradeAccuracy levels 0.05 or 0.01 for options
Source Output
AC Phase voltage output
Regulationfineness: 0.01% RG
Resolution:6 effective digits
Accuracy: better than 0.1% RG
Stability:better than 0.02%RG/ 2min
Distortion degree:<0.2% (noncapacitive load)
Output power: rated 25 VA/phase
Full load regulation rate: ≤0.01% RG
Range: 10V - 460V
Four gears: 57.7 V, 100 V, 220 V, 380 V,switch automatically
Long-term stability: ± 60 PPM/year
AC current output
Adjust fineness: 0.01% RG
Accuracy: better than 0.1% RG
Resolution: 6 effective digits
Stability:<0.02% RG / 1 min
Distortion degree:<0.5%
Output power: rated output 20VA/Phase
Full load regulation rate: 0.01% RG
Range: 1mA~24A
Gears: 0.2A, 1A, 5A, 20A, switch automatically
Power output
Accuracy: better than 0.1% RG
Stability: better than 0.02% RG / 1 min
Resolution: 6 effective digits ( active power, reactive power, apparent power)
Power factor
Adjusting range:-1 ~ 0 ~ + 1
Resolution: 0.00001;
Accuracy: 0.001
Phase angle
regulationrange: 0 ~ 359.99°
Resolution: 0.001°
Accuracy: 0.05°
Frequency
Adjusting range: 40 Hz ~ 70Hz
Resolution: 0.001 Hz
Accuracy: 0.005 Hz
Harmonic
Output 2~31thharmonic, each order can be overlappedand output simultaneously but total harmonic content should not exceed below limit:Harmonic orderVoltage harmonic maximum content percentage (relative to fundamental wave) 2-840%9-1530%16-3120%32-515%Content display accuracy: accuracy: 0.1%
Content resolution: 4 effective digits
Harmonic phaseregulation range: 0 ~ 359.99°(relative to fundamentalwave)
2. Technique parameters:
Output power impulse constant: 18000000x5/In( "In":current gear: 60(100),20,5,1,0.2)
Output impulse level: 5V
electricity meterinput impulse circuit: 1
electricity meterinput impulse level: <5V or Passive
electricity metererror display range: ±0.000%--±99.99%
electricity metererror display resolution: 0.001%
electricity metermeter constant input range: 6 effective digits, decimalsallowed
electricity meterregulation testing point: Imax,0.5 Imax,1.2Ib,1Ib,0.5 Ib,0.2 Ib,0.1 Ib,0.05 Ib,0.02 Ib,0.01 Ib
Power factor testing point that can be set: 1.0, 0.5L, 0.8C, 0.5C
Meter circling number setting: 1-99993. Usual output regulationset point:
Voltage test point: 10%,20%,50%,80%,100%,110%,120%.
Current test point 5%,10%,20%,30%,50%,70%,100%,120%.
Phase test point: 0.5L,0.8L,1.0,0.8C,0.5C
Three phase voltage currentamplitude adjustable, fineness: 10%,1%,0.1%,0.01%, max 125%
Phase and power factor of 3 phase voltage current adjustable, fineness: 10°1°0.1°0.01°
Phase of UB, UC to UA can also be regulated
Frequency regulation is together with three phase voltage/current: 5Hz, 1Hz, 01Hz, 0.01Hz
4. Power supply: Single phase AC 220V, 50/60Hz
5. Dimension and weight:480*600*178mm, 27Kg