Business Type:
Manufacturer/Factory,Trading Company
Business Range:
Fire Alarm Control Panel, FM200 System, Smoke Detector, Manual Call Point, Heat Detector, ..
Establishment:
2012
R&D Capacity:
OwnBrand, ODM, OEM
Terms of Payment:
LC, T/T, PayPal, WesternUnion
Main Markets:
North America, South America, Europe, Southeast Asia, Middle East, Africa
OEM/ODM Service
Sample Available

Fire Alarm System, Control System, Fire Alarm manufacturer / supplier in China, offering Wired Addressable Control Panel Fire Alarm System, 2-Wire Conventional Fire Alarm Control Panel for Hotel Use, Asenware Manufacturer Addressable Fire Alarm Control Panel for Office Building and so on.

1
    YRS
General Supplier

FM200 Gas Suppression Fire Fighting System

Get Latest Price
Min. Order / Reference FOB Price
1 Piece US $1000.00/ Piece
Local Area: Shenzhen, Guangdong, China
R&D Capacity: OEM, ODM, Other
Payment Terms: LC, T/T, PayPal, WesternUnion
Capacity: 70L/90L/100L/120L/150L/180L
Agent: Hfc-227ea
Pressure: 2.5/4.2/5.6MPa
FM200 Gas Suppression Fire Fighting System
The FM-200 Fire Suppression System is an engineered system utilizing a fixed nozzle agent distribution network. The system is designed and installed in accordance with the National Fire Protection Association (NFPA) Standard 2001, "Clean Agent Fire Extinguishing Systems." When properly designed, the FM-200 system will suppress surface burning fire in Class A, B, and C hazards.The clean agent fire extinguishing system shall perform as outlined in the following sub-sections.
A. Achieve a 6.25% (v/v) extinguishing concentration for Class A (Surface Type Fires) hazards.B. Achieve a 8.70% (v/v) or greater, as required, extinguishing concentration for Class B (Flammable Liquids) hazards.C. Achieve a 7.00% (v/v) extinguishing concentration for Class C (Energized Electrical Equipment) hazards.D. Within 10 seconds, the clean agent fire extinguishing system shall discharge 95% of the required suppression agent mass.E. The clean agent fire extinguishing system shall consist of one or more Asenware Fire Systems agent cylinders and related equipment. The cylinders may be either connected to a discharge pipe arrangement separately or connected to a common manifold and discharge pipe arrangement. The agent cylinders shall be filled with FM-200, and super pressurized with dry nitrogen to a working pressure of 360 PSIG at 70°F (24.8 bar gauge at 21°C).FM200 technical parameters
Tempreture ºC0-5020ºC Storage pressure(Mpa)
2.54.25.620ºCmaximum working pressure
(Mpa)
4.26.78Cylinder (L)10070/90/100/120/150/18090AGENT kg/m3≤1120≤1120≤1080Nozzal pressure≥0.6≥0.7≥0.8Discharge timeComputer room ≤8 others≤10concentration8-10%
FM 200 system operation
A. The clean agent fire extinguishing system shall consist of FM-200, agent cylinder(s), actuation hardware and discharge nozzle(s) attached to a pipe networkB Detection System - The ASENWARE Detection System is used where an automatic electronic detection system is required to actuate the FM-200 suppression system. This detection system is
used to actuate a single, fixed, fire suppression or alarm system based on inputs received from fire detection devices. The detection circuits can be configured using cross, counting, independent or priority-zone (counting) concepts. The detection system has been tested to the applicable FCC Rules and Regulations for Class A Computing devices.FM200 fire detection and suppression systems