Sensor Switch, Motion Switch, Motion Sensor Switch manufacturer / supplier in China, offering 360 Degree Ceiling PIR Infrared Motion Sensor Light Switch, High Sensitivity Co Gas Detector Carbon Monoxide Alarm for Home, Auto Carbon Monoxide Sensor with LCD Display and so on.
Min. Order / Reference FOB Price | |
---|---|
1 Pieces | US $142.00/ Pieces |
Local Area: | Shenzhen, Guangdong, China |
---|---|
R&D Capacity: | OEM, ODM, Other |
Payment Terms: | LC, T/T, PayPal |
Type: | Fire Alarm Control Panel |
---|---|
Anti-theft Alarm System Approach: | Passive |
Anti-Theft Alarm System Type: | Fire Alarm System |
Home Alarm System Conventional Fire Alarm Control Panel
Fire alarm control panelSR-P01-4 4zones conventional fire alarm control panelSR-P01-8 8zones conventional fire alarm control panelSR-P01-16 16 zones conventional fire alarm control panelThe SR-P01 Series Conventional Fire Alarm Control Panel is a24 volt, four to sixteen-zone, Class B, Conventional Fire Alarm Control Panel. Designed exclusively to meet the latest market requirements and future ULC codes, the highly cost-effective SR-P01 Series can be used in avariety of low- to mid-sized applications.
Main Features:
Four, Eight, Sixteen Zone Style B(Class B) Initiating Device Circuits (IDCs), All zones accept
two-wire smoke detectors and any normally-open contact devices.
Two Supervisory Input with DC12V output, ideal to connect security alarm devices.
Three General Alarm, Trouble and Supervisory, Form ARelay Output.
One, Two, Four Built-in Sound Output, Style Y(Class B) Notification Appliance (Signal) Circuits
(NACs), NACs may be programmed: Silenceable or Non-Silenceable.
3.0 amps of total system power. Resettable DC24V &Non-resettable DC24V Output.
Zone Input Short Circuit can be set to "Alarm" or "Fault" mode.
RS485 Communication Port (optional).
Automatic/Manual mode can be programmed.
Disable/Enable control per Zone (IDC) can be programmed.
Disable/Enable Sound Output(NACs) can be programmed.
Technical specification:
AC POWER: 220VAC, 50 Hz.
BATTERY: Sealed lead-acid batteries only. Maximum charging circuit: 27.6VDC @0.8 amp for
normal flat charge. Maximum battery charger capacity: 18AH battery.
NOTE: Two 10AH batteries can be housed in the cabinet. Larger batteries require aseparate
battery box.
Total DC24V system power: 3.0 amps.
Maximum current per NAC: 1.25 amps.
Maximum battery charging capability: 18 AH.
Resettable four-wire smoke detector power output.
Non-resettable power output.
Integral Form-A Alarm, Trouble and Supervisory relays, rated at: 2.0 amps @30 VDC
(resistive), 2.0 amps @30 VAC (resistive)
Product Pictures
* Sea and Air delivery is available
* welcome your agent to deal with our products .
Website: http:https://www.sumring.com