Business Type:
Manufacturer/Factory,Trading Company
Business Range:
High Voltage Tester, HV PD Test Set, HV Resonant Test System, Cable Fault Locator, SF6 Gas ..
Establishment:
2012
R&D Capacity:
OwnBrand, ODM, OEM
Terms of Payment:
LC, T/T, PayPal, WesternUnion
Main Markets:
North America, South America, Europe, Southeast Asia, Middle East, Africa, East Asia(Japan, South Korea), Australia, Domestic
OEM/ODM Service
Sample Available

High Voltage Tester, High Voltage Equipment, Withstand Voltage Tester manufacturer / supplier in China, offering Automatic AC High Voltage Test Set/Multi-channel Withstand Voltage Tester, GDKC-12A High Voltage Circuit Breaker Tester Transformer Test Device, GDHL-200B Factory Price Automatic Contact Resistance Tester Microhmmeter and so on.

1
    YRS
General Supplier

ISO Standard GDHG-106B CT PT Analyzer Transformer Tester

Get Latest Price
Min. Order / Reference FOB Price
1 Piece US $3000.00/ Piece
Local Area: Wuhan, Hubei, China
R&D Capacity: OEM, ODM, Other
Payment Terms: LC, T/T, PayPal, WesternUnion
Application: Electronic, Instrument
Type: CT/PT
Phase: Single

General introductionGDHG-106B CT/PT Analyzer is suitable for all types of CT and PT.For Laboratory and On-site test.
Features1. Finish all testing subject by itself, no need to connect auxiliary equipment.2. Built-in printer, to print results easily.3. Large screen LCD, graphically display.4. Auto display excitation knee point value, 5% and 10% error curve.5. Save 3000 groups data.6. With USB port. The data can be saved in USB disk and read by PC(WORD format file).7. Portable design about 35kg, suitable for on-site test.8. Engineering plastic box with damping, strong and reliable.
Specifications
CT(protectiontype,measurementtype)PT
Voltagecurrentcharacteristiccurve(excitationcharacteristic)Voltagecurrentcharacteristiccurve(excitationcharacteristic)
AutocalculatekneepointvalueAutocalculatekneepointvalue
Autodisplay5%and10%errorcurveTurnsratiomeasurement
TurnsratiomeasurementPolaritydetermination
RatioerrormeasurementRatioerrormeasurement
Phasemeasurement(angulardifference)Phasemeasurement(angulardifference)
PolaritydeterminationACwithstandtest
PrimarycurrentinjectiontestSecondarywindingresistancemeasurement
ACwithstandtestSecondaryburdenmeasurement
SecondarywindingresistancemeasurementDemagnetizationofironcore
Secondaryburdenmeasurement
Demagnetizationofironcore
ItemParameter
PowersupplyAC220V±10%,50Hz
Output0-2500Vrms,5Arms(20Apeak)
Outputcurrent0-1000A
Accuracyofexcitation≤0.5%(0.2%*thereading+0.3%*range)
SecondarywindingresistancemeasurementRange0~300Ω
Accuracy≤0.5%(0.2%*thereading+0.3%*range)
SecondaryactualburdenmeasurementRange0-1000VA
Accuracy≤0.5%(0.2%*thereading+0.3%*range)±0.1VA
Accuracyofangularerror4min
Accuracyofratioerror0.05%
CTratiomeasurementRange25000A/5A(5000A/1A)≥5A/5A
Accuracy≤0.5%
PTratiomeasurementRange≤500KV
Accuracy≤0.5%
OperationenvironmentTemperature:-10-40 degree,Humidity:≤90%,Altitude:≤1000m
Dimension&WeightDimension:440mmx340mmx380mm
Weight:≤35Kg