Business Type:
Manufacturer/Factory,Trading Company
Business Range:
AC Current Transducer, Power Transducer, Voltage Transmitter & other Analysis Instruments, ..
Establishment:
2004
R&D Capacity:
OwnBrand
Terms of Payment:
LC, T/T
Main Markets:
Southeast Asia, Middle East, Domestic
OEM/ODM Service
Sample Available

Test Bench, Mater Test Bench manufacturer / supplier in China, offering DEC-9100 Series Single-Phase Test Bench Selection, Juxta Frequency Transducers, Juxta Power Factor Transducers and so on.

1
    YRS
General Supplier

Juxta AC Watt Transducers

Get Latest Price
Min. Order / Reference FOB Price
1 Piece Contact Supplier
Local Area: Zhejiang, China
R&D Capacity: OEM, ODM, Other
Payment Terms: LC, T/T
Kind: Two-wire Transmitter
Type: AC Transmitter
Phase: Three
JUXTA AC WATT TRANSDUCERS1.GENERAL
The 2469 and 2489 AC Watt transducers produce an analog output equal to the Watts measured by the
input. The typical calibration is 500 Watts / element for 120V and 5A AC transformer secondary inputs.2.SPECIFICATIONS:Model #24692489Current input / range0-1 Amp AC or 0-5 Amp AC10 to 200% of rated input0-200% of rated inputCurrent input over range capability200% of rated input continuous
1000% of rated input for 5 secondsCurrent input burden< 0.2VA per elementVoltage inputs and range: Input powered range
Auxiliary powered range
Voltage input burden per element120V 240V
100-135VAC 200-264VAC
0-120% rated input
<0.5VA <1.0VA120V 240V
85-135VAC 170-264VAC
0-120% of rated input
<0.3VA <0.6VASustained Voltage input overange150% of rated input without damage (Auxiliary powered only)Rated outputs0 to ±1mADC into 10kWmax. load; 10VDC output compliance
4-20 mADC into 750Wmax. load; 15VDC output complianceAccuracy0 ± 1mADC = 0.5% of full scale
4-20mADC = 0.5% of span0±1mADC = ±0.1% rdg. ± 0.05%FS
4-20mADC = ±0.2% of spanOutput calibration / element120VAC: 1 Amp = 0-100 Watts; 5 Amp = 0-500 Watts
240VAC: 1 Amp = 0-200 Watts; 5 Amp = 0-1000 WattsExternal calibration adjustmentZero: ± 1%minimum
Span: ± 2%minimumZero: ± 5% minimum
Span: ± 10% minimumResponse time< 400 milliseconds (0-99% of output)Output ripple0.3% of span peak-to-peak max.0.5% of span peak-to-peak max.Isolation2500 VAC input to output, power and case2500 VAC input to output, power and caseSurge Withstand CapabilityIEEE472/ANSI C37.90.1 - 1989, JIS C1111 (5KV 1.2 x 50 microseconds)Insulation resistance> 10 megohm / 500VDC input/output/power/caseOperating temperature-20°C to +60°C1mA (-20°to+70°C), 4-20mA(-20°to+60°C)Operating humidity0 - 90% relative humidity (non-condensing)Temperature effect±250 PPM / °C of span1mA ±50FS, 4-20mA ±75span (PPM/°C)External magnetic field< 0.2% at 400 AT/mInfluence : unbalanced currents /
phase interaction / PowerFactor<0.5%<0.2%Influence of frequency<0.25%, 45-65 Hz, fundamental through 9th harmonicWeight1200g (2.65 lbs.)Shock<0.2% after 50G, 3 Axis and 6 repetitionsVibration<0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3 AxisUL RecognitionFile # E605793) STANDARD MODELS120 VAC, 5AAC, 60 Hz, input powered2469 (0.5% Accuracy)2489 (0.2% Accuracy)Watt 1P2W, 0-1mA output (1 Element) Watt 1P2W, 4-20mA output (1 Element) Watt 3P3W, 0-1mA output (2 Element) Watt 3P3W, 4-20mA output (2 Element) Watt3P4W,0-1mAoutput(21⁄2Element) Watt3P4W,4-20mAoutput(21⁄2Element) Watt 3P4W, 0-1mA output (3 Element) Watt 3P4W, 4-20mA output (3 Element)246951-540-AFA-0248951-540-AFA-0246951-540-AHD-0248951-540-AHD-0246953-540-AFA-0248953-540-AFA-0246953-540-AHD-0248953-540-AHD-0246954-540-AFA-0248954-540-AFA-0246954-540-AHD-0248954-540-AHD-0246955-540-AFA-0248955-540-AFA-0246955-540-AHD-0248955-540-AHD-0NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options.Auxiliary power supply options <5.0 VA burden.