Surge Protective Device:
Application range:
applied to equipotential bonding of the main low voltage distribution boxes in the building, providing overvoltage protection arising from the class Clightning strike to power supply system or misoperation. (Option from standard IEC61643- 1 and GB50343).
Main Feature:Plug and playdesign, live-wire replacement, easy maintenance;Build-in temperature control circuit breaker, high security performance;Green light in notice window indicates normal; red indicates broken, replacement notice, which is clear and easy distinguished;Optional telesignalling monitoring interface, realizable remote monitoring;External bus-bar wire, single module free assembled, easy project construction;Assembled 1P, 1P+N, 2P, 3P, 3P+N, 4P etc modes, applied to various electric network systems
Surge Protection Device LY3-C40/3+NPE
SPD to EN 61643-II
Type 2
SPD to IEC 61643-I
Class II
SPD to VDE 0675-6
Class C
Max. continuous voltage [L-N] Uc
275 V
Max. continuous voltage [N-PE] Uc
255 V
Nominal discharge current (8/20μs) In
20 kA
Max. discharge current (8/20μs) Imax
40 kA
Lightning impulse current (10/350) [N-PE] limp
≤ 12.5 kA
Voltage protection level [L-N] Up
≤ 1.5kV
Voltage protection level [N-PE] Up
≤ 1.2kV
Response time [L-N] tA
≤ 25 ns
Response time [N-PE] tA
≤ 100 ns
Max. back-up fuse
125 A gl/gG
Short-circuit withstand current
25kA/50Hz
Operating temperature range TU
-40 °C ^+80°C
Cross-sectional area (min.)
1.5 mm 2 solid / flexible
Cross-sectional area (max.)
35 mm 2 stranded / 25 mm 2 flexible
Mounting on
35 mm DIN rail acc. To EN 60715
Degree of protection
IP 20
Housing material
Thermoplastic; extinguishing degree UL 94 V-0
The color of pluggable module [L-N]
Gray (default), Red, Yellow
The color of pluggable module [N-PE]
Blue (default), Gray; without inspection window
The color of base
Gray
Floating remote signalling contact
No
Switch capacity
AC: 250V/0.5A; 125V/3 A
Cross-sectional area for remote signaling terminals
Max. 1.5 mm 2 solid / flexible