LXSG-B3 Multi-jet Dry Type Vane Wheel COLD/HOT with External Adjust Water meter
Features
With external regulating device
Magnetic drive, lower transmission resistance
Magnetic shield, use for external magnetic field protection
Evacuated and sealed dry dial register ensures clear reading
Central strainer
Inlet strainer
There are two versions DN50 meter body to be chosen: With threaded ends or flanged ends
Compliance with Standard
Technical data conforms to ISO 4064 Class B Standard for horizontal installation
Options
Meter with non return valve(different price) is available except ECO- LXSCE DN15-50
Meter for hot water up to 90°is available
Meter equipped with reed switch is available
Installation Requirements
The meter should be installed in horizontal position with the register face upwards
Pipeline must be flushed before installation
The meter should be constantly full of water during operationApplication
Measuring the volume of cold potable water passing through the pipeline
Working Conditions
Water temperature: ≤40ºC
Water pressure: ≤1.6MPa
Dimensions and WeightNominal diameterDN152025324050Body threadDG3https://4BG1BG11/4BG11/2BG2BG21/2BConnector threaddR1/2R3/4R1R11/4R11/2R2Body length mmL165190260/225260/230300/245300/280Overall length mmL1259294380/345384/354431/376448/428Width mmW94949898122145Meter height mmH107.5107.5117.5117.5141.5177Weight without connectors Kg1.51.72.6/2.42.8/2.75.1/4.88.5/8.2Weight with connectors Kg1.681.983.12/2.923.6/3.56.14/5.8410.22/9.92Nominal diameterDN1520Body length for selecting mmL110130145170190160DN50 (Flanged ends):11.5kg. L1 is the total length when coupling gaskets without compressionMain Technical DateNominal diameterDN132025324050Maximum flow rate m³/hQmax3.05.07.01220.030.0Nominal flow rate m³/hQn1.52.53.56.010.015.0Transition flow rate l/hQt1202002804808003000Minimum flow rate l/hQmin305070120200450Maximum reading m³ 99999.99995999999.99995/999999.9995Minimum reading m³ 0.000 050.00005/0.0005Maximum Permissible Error:
In the lower zone from Qmin inclusive up to but excluding Qt is ±5%
In the upper zone from Qt inclusive up to and including Qmax is ±2%