General introduction
GDLP series Transmission Line Test System is a new generation power transmission line frequency parameter testing system. It integrated with frequency conversion testing power, precise measuring module and DSP high speed digital processing chip, which eliminate strong interference and ensure the safety of equipment, with convenient, fast and accurate measure.
Features
1. Quickly and accurately test the positive sequence capacitance, the positive sequence impedance, zero sequence capacitance, zero sequence impedance, also can measure the mutual inductance and coupling capacitance between lines;
2. High Anti-interference ability, ensure high-precision, accurate and reliable measurement;
3. Easy operation, equipped with full large LCD touch screen, shows every operation steps;
4. Simple wiring, only connecting with tested down leads to finish all line parameters measurement;
5. New generation ARM embedded system as inner core, solving the problem of system halted;
6. High integration with testing power supply, instrument, computational model;
7. DSP high speed digital signal processor as processing core, fast and Accurate testing process;
8. Can save 100 groups testing data, data management and report generation through USB interface to PC;
9. Light weight, 30kg lighter than similar product, no need to split;
10. Suitable for occasions of power supplied by generator when the power is 11. Two phase line measurement (including DC transmission lines and electrified railway traction lines).
Technical Parameters
Power supplySingle phase, 220V±10%Inner pilot frequency power supplyMax. Output voltageThree phase, 200V (RMS, <±1%)Max. Output current8AOutput frequency45Hz, 55HzMeasuring rangeCapacitance: 0.1 ~ 50uF;
Impedance: 0.1 ~ 400ohm;
Impedance Angle: -90 ~ +90 degreeMeasurement ResolutionCapacitance: 0.0001uF;
Impedance: 0.0001ohm;
Impedance angle: 0.0001degreeAccuracyMeasuring voltage: ± 0.5% of the reading ±0.01V;
Measuring current: ± 0.5% of the reading ±0.01A;
Capacitance: >=1uF, +/-1% of the reading ±0.01uF;
< 1uF, ±2% of reading ± 0.01uF;
Impedance: ≥1ohm, ±1% of the reading ± 0.01ohm;
< 1ohm, ±2% of reading ± 0.01ohm;
Impedance Angle: ± 0.2degree (voltage> 1.0V);
± 0.3degree(voltage: 0.2V -1.0V);Protection functionOver-current:
Power output over-current protection (greater than 150% of rated output)
Interference currents greater than 40A, the instrument protection;
Overvoltage Protection:
Power output overvoltage protection (greater than 150% of rated output)
Voltage rise on time (rise slope greater than 15V/ms) protection
Induced interference voltage is greater than 350V, protection.Grouding protectionBefore testing and after testing, all test terminals connect with ground automatically which ensure instrument and operation person's safety.Waveform aberration rateSine wave, aberration rate<2%;Insulation performance, anti-shock performance;Insulated resistance(MΩ )Power input terminal >10 MΩ
Current input terminal >10 MΩ
Voltage input terminal >10 MΩWithstand voltage strength1.5kV, 1min, no breakdown arcing;
After doing 0.5m falling test, can still rest stably and reliably.Anti-interference parameterInterference voltage: Anti-interference voltage up to 20KV;
Interference current: When short circuit grounding, <40A;
Test stably and accurately in the condition of output signal and interference signal ratio with 1: 10Dimension500mm(L)*400(W)*450mm(H)Weight45kg