General
1. Protection against the effects of sinusoidal alternating earth fault currents
2. Protection against indirect contacts and additional protection against direct contacts
3. Protection against fire hazard caused by insulation faults
4. Controlling and Switching
5. Used in residential building, non-residential building, energy sources, industry and infrastructure
Electrical featuresRated current InA16, 25, 32, 40, 50, 63AType (wave form of the earth leakage sensed)
A,ACPolesP2,4Rated voltage UeV240/415Insulation voltage UiV500Rated frequencyHz50/60Rated breaking capacity Inc=IΔcA4500,6000SCPD fuseA6000Rated impulse withstand voltage (1.2/50) UimpV6000Dielectric test voltage at ind. Freq. for 1minkV2.5Rated sensitivity IΔ nA0.03, 0.1, 0.3Rated residual making and breaking capacity IΔ mA500(In≤40A); 630(In>40A)Pollution degree
2Mechanical featuresElectrical lifet4000Mechanical lifet8000Protection degree
IP20Storage temperature° C-25~+70Ambient temperature (with daily average≤35° C)° C-5~+40InstallationTerminal connection type
Cable / U-type bar / Pin-type busbarTerminal size top/bottom for cable mm225AWG18-3Terminal size top/bottom for busbarmm225AWG 18-3Tightening torqueN*m2.5In-Ibs.18Mounting
On DIN rail EN 60715(35mm) by means of fast clip deviceConnection
from top and bottom