Newest Designed YCC1(LCD1/CJX2) 380V AC brands electric contactors
General
YCC1 series AC Contactor is suitable for using in the circuits the rated voltage up to 690V AC, 50Hz or 60Hz. Rated current up to 95A with AC-3 type. YCC1 is used to connect&break circuit with long distance, meanwhile combining with matchable thermal relay as a electromagnetic starter to protect circuit in case over-load happened.
YCC1-N series reversible AC Contactor is suitable for using in the circuits the rated voltage up to 690V, rated current up to 95A, frequency is 50Hz or 60Hz and used in motor reversible controlling. Mechanical interlock of it can ensure the reliability for two reversible contacts' shift.
Standard:IEC60947-4-1,GB14048.4
Specification
Table 1
TypeYCC1-D09YCC1-D12YCC1-D18YCC1-D25YCC1-D32Rated operational
current (A)380VAC-3912182532AC-43.557.78.512360VAC-36.68.9121821AC-41.523.84.47.5Rated conventional thermal current (A)2020324050Rated insulation voltage (V)690690690690690Rated operational
power in category
AC-3kw220V2.2345.57.5380V45.57.51115660V5.57.5101518.5Intermittent periodic duty-type
motor frequency AC-4kw380V1.52.2345.5660V1.11.53.745.5Operation cycles
(times/hour)ElectricalAC-31200120012001200600AC-4300300300300300Mechanical36003600360036003600Electrical life (X 10³times)AC-310010010010080AC-42020202020Mechanical life(X 10³times)1000100010001000800Matching fuse modelRT16-20RT16-32RT16-40RT16-50Screw sizeM3.5M3.5M3.5M4 M4M4 M4Tightening torque(N·m)0.80.80.81.2 1.21.2 1.2Power of AC coil50HzClose(VA)707070110110Remain(VA)999.51414.0Power(W)1.8-2.71.8-2.73-43-43-4Power of DC coilPower(W)99111111Operation rangeVoltage of closing: 85%Us-110%Us; Voltage of releasing: 20%Us-75%Us, DC:10%Us-75%UslSpecification of auxiliary contactsAC-15: 360VA DC-13: 33W Ith: 10A
Table2
TypeYCC1-D40YCC1-D50YCC1-D65YCC1-D80YCC1-D95Rated operational
current (A)380VAC-34050658095AC-418.524283744360VAC-33439424949AC-49121417.321.3Rated conventional thermal current (A)6080809595Rated insulation voltage (V)690690690690690Rated operational
power in category
AC-3kw220V111518.52225380V18.522303745660V3037374545Intermittent periodic duty-type
motor frequency AC-4kw380V7.5111518.522660V7.511111518.5Operation cycles
(times/hour)ElectricalAC-3600600600600600AC-4300300300300300Mechanical36003600360036003600Electrical life (X 10³times)AC-38060606060AC-41515151010Mechanical life(X 10³times)800800800600600Matching fuse modelRT16-63RT16-80RT16-80RT16-100RT16-125Screw sizeM4/M8M8M8M8/M10M10Tightening torque(N·m)1.2/3.53.53.53.5/4.04.0Power of AC coil50HzClose(VA)200200200200200Remain(VA)5757575757Power(W)6-106-106-106-106-10Power of DC coilPower(W)2020202020Operation rangeVoltage of closing: 85%Us-110%Us; Voltage of releasing: 20%Us-75%Us, DC:10%Us-75%UslSpecification of auxiliary contactsAC-15: 360VA DC-13: 33W Ith: 10A